46
L20, L30
Chg. Cur. Limiting Coef.: The charging current limit is a multiple of the battery capacity.
The value can be 0.05–0.15 and is 0.15 by default.
Cell float volt: The float voltage value can be 2.20-2.29 V/cell and is 2.25 V/cell by
default.
Cell boost volt: The battery equalized voltage value can be 2.30–2.40 V/cell and is2.30
V/cell by default.
Aver charging Duration: boost charge time limit, the value can be 1–999 min, and is 240
by default.
EOD Battery Volt(V/Cell): End of discharge voltage. The value can be 1.60~1.90 andis
1.67 by default.