RS485 Bus Configuration
To connect to the monitoring platform:
1. Designate a single inverter as the connection point between the RS485 bus and the
monitoring platform. This inverter will serve as the leader inverter.
2. Connect the leader to the monitoring platform using Ethernet (refer to
Creating an
Ethernet (LAN) Connection
above).
To configure the RS485 bus:
All inverters are configured by default as followers. To configure the leader:
1. Make sure the inverter's ON/OFF/P switch is off.
2. Make sure that the AC circuit breaker on the main distribution panel is on.
3. Turn on the DC Safety Unit.
4. Turn on the DC Safety Unit (if applicable).
5. Access SetApp, as described in
Communication
on page 42.
6.
From the Commissioning screen, select Site Communication > RS485-1 > Protocol
> SolarEdge > SolarEdge Leader.
7.
Return to the RS485-1 screen and select Follower Detect.
The system starts automatic detection of the follower inverters connected to the
leader inverter. The inverter should report the correct number of followers. If it does
not, verify the connections and terminations in all inverters in the chain.
8. To check the follower IDs and last communication time, select RS485-1 > Follower
List.
9. Verify the connection of the leader to the monitoring platform, as described below.
Verifying the Connection
After connecting and configuring a communication option, perform the following
steps to check that the connection to the monitoring server has been successfully
established.
1.
If the DC Safety Unit cover is not closed, close it: Attach the DC Safety Unit cover
and secure it by tightening the screws with a torque of 10.3 N*m/ 7.6 lb.*ft.For
proper sealing, first tighten the corner screws and then the two central screws.
Access SetApp and selectCommissioning >Status.
2. In the Summary section, under Server Comm., make sure S_OK is displayed
together with the selected communication option.
Three Phase Inverter with SetApp Configuration PN: SEXXK-XXXXIXXXX
57 RS485 Bus Configuration

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolarEdge SE Series and is the answer not in the manual?

SolarEdge SE Series Specifications

General IconGeneral
EfficiencyUp to 99%
Protection RatingIP65
CommunicationEthernet, Wi-Fi (optional), RS485
DimensionsVaries by model
WeightVaries by model
Rated AC PowerVaries by model
Max. DC PowerVaries by model
ModelSE Series (e.g., SE3000H, SE5000H)
AC Output PowerVaries by model
MPPT RangeVaries by model
Operating Temperature-25°C to 60°C
Warranty12 years standard, extendable to 20 or 25 years

Related product manuals