SE33.3K SE40K Unit
Applicable to inverters with
part numbers
SEXXK-XXX8IXXXX
Dimensions with Safety Unit
(HxWxD)
839 x 328 x 300
mm
Weight 32 kg
Weight with Safety Unit 36.5 kg
Operating Temperature Range
(1)
-40 to +60 ˚C
Cooling Fan (user replaceable)
Noise < 62 dBA
Protection rating /
Environmental category
IP65
Pollution degree classification
(inside / outside)
2/3
Mounting bracket Mounting Bracket Provided
Average Short Circuit Current During Fault
(2)
Inverter Model Ip Ik'' Ik
SE25K (400 L-L) 54.45 38.5 37
SE27.6K (400 L-L) 58.55 42.55 40.9
SE30.K (400 L-L) 66.4 47 44.3
SE33.3K (400 L-L) 71.1 50.95 48.7
SE33.3K (480 L-L) 58.55 42.55 40.9
SE40K (480 L-L) 71.1 50.95 48.7
(1)
See Temperature de-rating - Technical Note at:
https://www.solaredge.com/sites/default/files/se-temperature-derating-note.pdf
(2)
Ip: Short-circuit peak current, in amplitude
Ik'': Initial symmetrical short-circuit current , in RMS
Ik: Short-circuit steady state current, in RMS
Technical Specifications - Three Phase Inverters for Europe &APAC for
220/380V, and 230/400V Grids 78
Three Phase Inverter with SetApp Configuration PN: SEXXK-XXXXIXXXX