EasyManuals Logo

SolarEdge SE3000 User Manual

SolarEdge SE3000
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #97 background imageLoading...
Page #97 background image
Figure 41: DC terminals
3.
Connect the AC wires according to the labels on the ACterminal blocks, as follows:
Wire type Connect to terminal
Figure 42: AC terminals
Line 1 L1
Line 2 L2
Line 3 L3
PE (grounding)
Neutral N
4. Tighten the screws of each terminal with a torque of 1.2-1.5 N*m / 0.88-1.1 lb.*ft.
5. Verify that there are no unconnected wires at the output of the DC Safety Unit and
that any unused terminal screws are tightened.
6. Connect the DC and AC wires to the DC Safety Unit. Refer to
Connecting the AC and
the Strings to the Inverter
on page 31.
7. Ensure proper cable entry sealing; inspect the entire cable run and use standard
sealants to avoid water penetration.
-Three Phase System Installation Guide MAN-01-00057-4.1
96 Replacing the DC Safety Unit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolarEdge SE3000 and is the answer not in the manual?

SolarEdge SE3000 Specifications

General IconGeneral
ModelSE3000
ManufacturerSolarEdge
AC Output Power3000 W
CoolingNatural Convection
Protection RatingIP65
Rated AC Power3000 W
Max. AC Power3000 VA
Maximum Output Current13 A
Number of MPP Trackers1
Operating Temperature Range-25°C to 60°C
AC Voltage230 V
Max. Input DC Voltage480 V

Related product manuals