To check Backup:
1.
DisconnecttheACpowerbyshuttingofftheACatthemaindistributionpanel.Theinvertershould
disconnectfromthegrid,andcontinuesupplyingpowertothebacked-uploads.
SwitchingtoBackupmodetakesafewseconds.TheLCDscreenwillshowthaBackupmodeisON:
V a c [ V ] V d c [ V ] P a c [ W ]
2 4 0 . 7 3 7 1 . 9 2 3 4 9 . 3
P _ O K : X X X / Y Y Y < S _ O K >
B a c k u p M o d e O N
2.
PresstheexternalLCDlightbuttontodisplaythebatterystatusscreen,andcheckthat:
l ThebatteryStateis:Discharging/Charging
l TheSOEpercentageisdecreasing/increasing
l ThePWRvalueisgreaterthan0
B S N : X X X X X X X X X I D : 2 4
S O E : 8 9 % W W W W W P W R : 3 W
T o t a l : < x > W h
S t a t e : D i s c h a r g i n g
3.
TurntheACbackONfromthemaindistributionpanel.Theinvertershouldreconnectloadsbackto
thegrid.
To check Maximize Self-consumption mode:
1. VerifytheinverterON/OFFswitchisON.
2. Turnonasmanyloadssothatconsumptionisgreaterthantheinverter'smaximumACpower.
3. PresstheinverterLCDlightbuttontodisplaytheMeterstatusscreenandcheckthatimportpoweris
greaterthanzero:
I m p o r t M e t e r
S t a t u s : < O K / E r r o r # >
P o w e r [ W ] : x x x x x . x
E n e r g y [ W h ] : X X X X X . X
4. PresstheinverterLCDlightbuttontodisplaytheSmartEnergyManagementandtheBatterystatus
screens,andcheckthat:
o
State=Discharging(assumingconsumption>PVproduction;invertermaximumACpower>PV
production.
o
PWR>0
B S N : X X X X X X X X X I D : 2 4
S O E : 8 9 % W W W W W P W R : 2 W
T o t a l : < X > W h
S t a t e : D i s c h a r g i n g