60
Parameter Unit China Israel Australia Others
Mains check
On/Off On On On On
- Vac MC max V242 264 264253
- Vac MC min V187 207 207196
- f MC max Hz 50.5 54.5 54.5 51
- f MC min Hz 49.5 45.5 45.5 47
- t MC monitoring s60 300 6030
Island Detection On/Off On On On On
Pac progression %/min Off Off Off Off
P(f)-Mode 2/3/Off Off Off Off Off
- f start Hz 50.2 50.2 50.2 50.2
- Reduction %/Hz 40 40 40 40
- Re-increase %/min10101010
Q-Mode Off Off Off Off
- Vac Lock On/Off Off Off Off Off
- Vac Lock-In V 253 253 253 253
- Vac Lock-Out V 207 207 207 207
S max SM2000S VA 1980 1980 1980 1980
S max SM3000S VA 2750 2750 2750 2750
S max SM4200S VA 4180 4180 4180 4180
S max SM6000S VA 5060 5060 5060 5060
Pac max SM2000S W 1980 1980 1980 1980
Pac max SM3000S W 2750 2750 2750 2750
Pac max SM4200S W 4180 4180 4180 4180
Pac max SM6000S W 5060 5060 5060 5060
Iac max SM2000S A12 12 1212
Iac max SM3000S A12 12 1212
Iac max SM4200S A19 19 1919
Iac max SM6000S A22222222