Installation Installation
d) Crimp pin contact by using the .MC4 crimping tool
(recommended model: H4TC0001, manufacturer: Amphenol)
MC4 crimping tool
( )
2 2
4mm - 6mm
Insert the wire into plug forcibly, when aclick is felt or heard, the pin contact
assembly is seated correctly.
e) Separate the DC connector as two parts: the plug and the cable nut.
f) Then tighten the cable nut.
g) Use a multimeter to measure the open circuit voltage of the positive pole
and negative pole of the PV cable, and make sure the open circuit voltage
600 V (Otherwise the machine may be damaged);
h) Remove the blue protective cover of the PV +&- interface at the bottom of
the inverter, and insert the completed PV terminals according to the positive
and negative correspondence.
I) Cover the remaining unused PV terminals with the original blue cover.
NOTE: Keep the DC switch of the inverter off during connection.
Grid Connection
Ø
The inverter is designed for single phase grid. The nominal grid voltage
is 220/ 230/ 240 V and the frequency is 50/ 60 Hz. Other technical
requests should comply with the requirement of the local public grid.
Table 4 Cable and Micro-breaker recommended
L,N Cable
4-6 mm²
Inverter+BMU
PE Cable
4-6 mm² 4-6 mm² 5-6 mm² 5-6 mm² 5-6 mm²
Micro-breaker
20 A 20 A 20 A 25 A 32 A 32 A
4-6 mm² 4-6 mm² 4-6 mm² 5-6 mm² 5-6 mm² 5-6 mm²
X1-6K-T-D(L)
X1-6K-T-N
Model
X1-
BOOST
-3K-G4
X1-
BOOST-
3.3K-G4
X1-
BOOST-
3.6K-G4
X1-
BOOST-
4.2K-G4
X1-
BOOST
-5K-G4
X1-
BOOST-
6K-G4
4-6 mm²
20 A
4-6 mm²
X1-
BOOST-
2.5K-G4
The parameters vary because of different environment and material. Please choose
appropriate cable and micro-breaker according to the local laws and regulations.