Mains cable (AC line cable) shall be short-circuit protected and thermal overload
protected.
Always fit the input cable with fuse. Normal gG (US: CC or T) fuses will protect the
input cable in short circuit situation. They will also prevent damage to adjoining
equipment.
Dimension the fuses according to local safety regulations, appropriate input
voltage and the related current of the solar inverter.
AC output protected by external fuse (gG rated current 16 A/600 VAC for 3 kW/4
kW/5 kW/6 kW; 25 A/600 VAC for 8 kW/10 kW; 40 A/600 VAC for 12 kW/15 kW)
provides in all live connections to the AC supply.
The rated short-circuit breaking capacity of the above protective device shall be
at least equal to the prospective fault current at the point of installation. See
section technical data of this manual for details.
2 2
AC output cable: Cu; R, S, T, N+PE: 3*4.0 mm +4.0 mm for 3 kW/4 kW/5 kW and
2 2 2 2
3*5.3 mm +5.3 mm for 6 kW/8 kW/10 kW, 3*6 mm +6 mm for 12 kW/15 kW
@40 ambient temperature with a max length of 5 m, with operating time of
the fuses is less than 5 seconds, installation method B2 according to EN60204-
1:2006, annex D: cable in conduit cable trunking system, number of loaded
circuit only one. Use H07RNF (cord designation 60245 IEC66) for an ambient
temperature of 40 or less and use 90 wire for ambient temperature between
40 and 60 .
Selection of Fuses and Cables Connection
Earth Connection
Ø
Screw allen wrench the ground screw with the shown as follows.
5.5.2 Communication interface
This product has a series of communication interfaces: such as WiFi,
RS485/Meter, DRM and USB for upgrading for human and machine
communication. Operating information like output voltage, current,
frequency, faulty information, etc., can be delivered to PC or other
monitoring equipment via these interfaces.
WiFi (Standard) /LAN (Optional)
This inverter provides a WiFi/LAN connecting port(the DONGLE port) which
can collect information from inverter including status, performance and
updating information to monitoring website via connecting Pocket WiFi
(Pocket LAN can be purchased from the supplier for optional if needed)
Connection steps:
Please check the Pocket WiFi user manual for more details.
Installation Installation
24
25
torque: 1.2±0.1N·m
Therefore the current-carrying capacity of the components and sub-assemblies
provided in the end-use system(connectors, cables, junction box, switchgear,
etc.) and the reverse current PV modules shall be considered based on the
feedback current and reverse current. The direct current(DC) circuit breaker or
fuse between each solar generator and inverter shall be provided based on
solar inverter input ratings.
Select DC cables based on the above inverter back-feed current and ISC PV
rating and Vmax ratings.
1. For condition differing from those mentioned above,
dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the unit.
(You can choose a thicker cable but the fuses must be rated
according to the rating of the cable.)
2. Fuses must be approved by Notified Body.
3. The AC output cable would be better to use the soft wire.
Note!