Menu Description
33
3333
33
MODE
MODE
MODE
MODE
MODE
UPON INITIATION
PARAMETERS DISPLAY
PAGE 1 PAGE 2 PAGE 3 PAGE 4
I1 I2 I3
0 0 0 %
MAIN & PROTECT.
PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT
PARAMETERS
SELECT
SELECT
SELECT
SELECT
SELECT
PRESS KEYS TO CHANGE PARAMETER VALUE
I1 I2 I3
0 0 0 A
STARTER FLC
150 AMP
SOFT START CURVE
1 (STANDARD)
SOFT STOP CURVE
1 (STANDARD)
DA: INIT. VOLT.
30%
OPTION CARD
NOT INSTALLED
MOTOR FLA
150 AMP
PULSE LEVEL
70% OF FLA
DEC. TIME
0 SEC.
DA: CUR. LIMIT
400% OF FLA
UNDERCURR. TRIP
0% OF FLA
PULSE TIME
0.0 SEC.
FINAL TORQUE
0 (MIN).
DA: ACC. TIME
10 SEC.
UNDERCURR. DELAY
10 SEC
INITIAL VOLTAGE
30%
STORE ENABLE
STOP PARAMETERS
DA: DEC. TIME
0 SEC.
O/C – SHEAR PIN
850% OF FLA
***INITIAL CURRENT
100% OF FLA
DA: MOTOR FLA
150 AMP.
O/C DELAY
0.5 SEC
CURRENT LIMIT
400% OF FLA
STORE ENABLE
D. ADJ/ PARAMETERS
OVERLOAD TRIP
115% OF FLA
ACC. TIME
10 SEC.
OVERLOAD DELAY
4 SEC. – AT 5 FLA
MAX START TIME
30 SEC.
UNBALANCE TRIP
20%
NUMBER OF STARTS
1
UNBALANCE DELAY
5 SEC.
STARTS PERIOD
20 MIN.
GND FAULT TRIP
20% OF FLA
START INHIBIT
15 MIN.
GND FAULT DELAY
5 SEC.
RUN CONTACT DEL.
5 SEC.
UNDERVOLT. TRIP
70% OF Un
STORE ENABLE START
PARAMETERS
UNDERVOLT. DELAY
5 SEC.
OVERVOLT. TRIP
120% OF Un.
OVERVOL. DELAY
2 SEC.
STORE ENABLE
MAIN & PROTECT.
*** The display will be
change automatically
when initial voltage will
increase over 50% of Un