EasyManua.ls Logo

Solcon RVS-DX Series - User Manual

Solcon RVS-DX Series
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
R
R
V
V
S
S
-
-
D
D
X
X
D
D
i
i
g
g
i
i
t
t
a
a
l
l
S
S
o
o
f
f
t
t
S
S
t
t
a
a
r
r
t
t
e
e
r
r
w
w
i
i
t
t
h
h
i
i
n
n
t
t
e
e
r
r
n
n
a
a
l
l
B
B
y
y
P
P
a
a
s
s
s
s
8
8
-
-
1
1
1
1
0
0
0
0
A
A
,
,
2
2
2
2
0
0
-
-
6
6
9
9
0
0
V
V
I
I
n
n
s
s
t
t
r
r
u
u
c
c
t
t
i
i
o
o
n
n
M
M
a
a
n
n
u
u
a
a
l
l
1B
Ver. 26/12/2012

Table of Contents

Questions and Answers

  • T
    Tiffany EricksonAug 20, 2025
    What to do if my Solcon RVS-DX Controller trips with an O/C SHEAR error?
    • J
      Jonathon LangAug 20, 2025
      If the Solcon Controller trips due to an O/C SHEAR fault, it means the current instantaneously exceeded 8.5 times the Starter FLC. First, verify the motor is properly installed and not jammed. Then, check the FLA and FLC settings. After that, inspect the motor and cable connections. Finally, perform a “Megger” test to assess the condition of the motor and cable.
  • R
    ryan60Aug 22, 2025
    Why does my Solcon Controller trip due to OVERLOAD?
    • J
      John VillarrealAug 22, 2025
      If your Solcon Controller trips due to an OVERLOAD, it means the current exceeded the OVERLOAD TRIP level and the thermal register has filled up. You should check the FLA, FLC, and Overload settings. Also, check the motor current and wait 15 minutes to allow the motor and starter to cool down before restarting.
  • J
    josephjohnsonAug 25, 2025
    What does it mean when my Solcon RVS-DX Controller trips with O/C or WRONG?
    • L
      Lisa JacksonAug 25, 2025
      If the Solcon RVS-DX trips due to O/C or WRONG, it indicates a wrong connection inside Delta or an overcurrent detection. Verify that the motor is not stalled or shorted, and check the cables and wiring. Also, ensure that the motor and RVS-DX are connected exactly as shown in section 4.3.9.2 page 13. If the circuitry is confirmed to be 100% correct, you can start when WIDER SETTINGS are ENABLED.
  • K
    Kelly Weaver DDSAug 26, 2025
    How to fix a PHASE LOSS trip on my Solcon RVS-DX?
    • T
      Thomas ThomasAug 26, 2025
      If the Solcon Controller trips due to PHASE LOSS, it means one or two phases are missing. Check that the voltages are within the required range and the frequency is within the range of 45-65Hz. If all previous actions do not solve the problem and you are sure that no real phase loss exists, you can set PHASE LOSS Y/N protection to NO.
  • K
    Kenneth SheppardAug 27, 2025
    What causes an UNDER/NO trip on a Solcon RVS-DX and how to resolve it?
    • R
      Ronald VargasAug 28, 2025
      If the Solcon Controller trips due to UNDER/NO, it means the line voltage dropped below the preset level for the preset time. Check the UNDER VOLTAGE TRIP and TIME DELAY settings, and verify the line voltages on L1, L2, L3.
  • R
    ricedavidAug 29, 2025
    Why does my Solcon Controller show an OVER voltage trip?
    • D
      Diana GarciaAug 29, 2025
      If the Solcon Controller trips due to OVER, it indicates that the line voltage increased above a preset level for a preset time. Check the OVER VOLTAGE TRIP and TIME DELAY settings, and verify the line voltage on L1, L2, L3.
  • A
    Angela McdanielAug 31, 2025
    What to do if Solcon Controller trips due to TOO MANY starts?
    • R
      Rebecca HillAug 31, 2025
      If the Solcon Controller trips because of TOO MANY trips, it means the number of starts during the START PERIOD exceeded the preset STARTS number. Wait until the motor and starter cool down – according to the START INHIBIT setting.
  • M
    mkleinSep 2, 2025
    Why is my Solcon RVS-DX Controller tripping with a LONG START error?
    • C
      christine74Sep 2, 2025
      If the Solcon Controller trips due to a LONG START, it means the output voltage did not reach nominal at the present MAX. START TIME. Check the FLA, FLC, and MAX START TIME settings. Increase the INITIAL VOLTAGE, CURRENT LIMIT & MAX. START TIME or decrease the ACCELERATION TIME as necessary.
  • L
    Lindsay RamosSep 4, 2025
    How do I resolve a PHASE trip on my Solcon Controller?
    • R
      Rachel CaseySep 4, 2025
      If the Solcon Controller trips due to PHASE, it means the line phase sequence is wrong. Check the line phase sequence, and if it is wrong, swap two wires on the line side.
  • E
    erin87Sep 6, 2025
    What does an UNDER current trip indicate on my Solcon RVS-DX?
    • N
      nsullivanSep 6, 2025
      If the Solcon Controller trips due to UNDER, it means the line current dropped below the preset level for the preset time. Check the UNDER CURRENT TRIP and TIME DELAY settings, and verify the line currents through L1, L2, L3.

Summary

2. Safety & Warnings

2.1 Safety

General safety precautions for operating the equipment and following manual instructions.

2.3 Warnings

Critical warnings regarding electrical hazards, internal components, and connections.

3. Technical Data

3.2 Rating and frames sizes

Table detailing starter types, frame sizes, dimensions, and weight.

3.3 Starter Selection

Criteria for selecting the appropriate starter based on motor FLA and conditions.

3.3.1 Motor current & Starting Conditions

Guidance on selecting starters based on motor FLA and starting parameters.

3.3.5 Starter selection tables for various voltage ratings

Tables for selecting starters based on voltage and motor power ratings.

3.3.5.1 Starter selection for 230 V, 400 V, 480 V, 600 V

Detailed selection table for specific voltage ratings and motor kW.

3.3.6 Ordering Information

Guide for specifying and ordering RVS-DX starters with options.

4. Recommended Wiring Scheme

4.1 Typical wiring diagram

Schematic showing standard RVS-DX electrical connections.

4.2 Power wiring scheme for Inside-Delta Connection

Wiring diagrams for connecting the RVS-DX in an "Inside-Delta" configuration.

4.3 Wiring Notes

Important notes and warnings for wiring the RVS-DX, including isolation.

4.3.1 Short Circuit Protection

Recommended fuses and protection for short circuits based on coordination class.

4.3.4 Start;Stop Input (terminal B1)

How to use the start/stop input terminals for motor control.

4.3.5 Aux. Input (terminal C1)

Programming options for the auxiliary input terminal C1.

4.3.6 Auxiliary output relay (terminals 13, 14)

Functionality and modes of the auxiliary output relay.

4.3.7 Fault Contact (terminals 23, 24)

Description of the fault contact and its operation modes.

4.3.8.2 RS-485 Communication (option # 3 M)

Details on RS-485 Modbus communication setup and wiring.

4.3.9 Inside-Delta mode

Explanation of the "Inside-Delta" connection method and its benefits.

4.3.9.2 Notes on Inside Delta” connection

Important notes and warnings for "Inside Delta" connection, including risks.

6. Installation

6.1 Prior to Installation

Checks to perform before installing the RVS-DX starter.

6.2 Mounting

Guidelines for mounting the RVS-DX starter vertically for optimal airflow.

7. Control Keypad

7.4 Reviewing and Modifying Parameters

Procedure for navigating and changing parameters using keypad.

7.5.3 Obtain Default Parameters

How to restore factory default parameter settings.

7.6.3 Main Parameters - page 1

Configuration of main parameters like Language, FLC, Motor FLA.

7.6.4 Start Parameters - page 2

Configuration of start parameters like Soft Start Curve and Initial Voltage.

7.6.5 Stop Parameters - page 3

Configuration of stop parameters like Soft Stop Curve and Deceleration Time.

7.6.8 Fault Parameters - page 6

Configuration of fault protection parameters like Phase Loss.

7.7.6 Fault and Reset Procedures

Procedure for handling faults and resetting the starter.

8. Starting Procedure

8.2 Standard Starting Procedure

Step-by-step guide for a standard motor start-up.

9. Trouble Shooting

Fault Massage Overview

Common fault messages displayed on the LCD.

Cause and Troubleshooting Steps

Troubleshooting steps for common faults like TOO MANY STARTS.

10. Technical Specifications

Motor Protection Summary

Summary of motor protection features and their trip conditions.

Solcon RVS-DX Series Specifications

General IconGeneral
TypeSoft Starter
Voltage208-690V AC
Frequency50/60 Hz
Ambient Temperature-10°C to +50°C
Control MethodVoltage Ramp
ProtectionOverload, Phase Loss
CommunicationModbus RTU
Enclosure RatingIP00, IP20, IP54

Related product manuals