EasyManuals Logo

Solcon RVS-DX Series User Manual

Solcon RVS-DX Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
39 Control Keypad
___________________________________________________________________________________________
7.6.7.1 WIDER SETTINGS Parameters:
Parameter
WIDER SETTINGS Disabled
WIDER SETTINGS Enabled
INITIAL VOLTAGE
10-50%
5
(1)
-80%
CURRENT LIMIT
100-400%
100-500%
ACCELERATION TIME
1-30 seconds
1-90 seconds
DECELERATION TIME
0-30 seconds
0-90 seconds
MAX. START TIME
1-30 seconds
1-250 seconds
PHASE LOSS Y/N
Yes
(2)
Yes/No
(2)
MAX SLOW SP TIME
1-30 seconds
1-250 seconds
O/C or WRONG CON protection
in Inside Delta mode.
Protection active in normal set
(3)
Protection active in high set
(3)
OVERLOAD TRIP protection.
OVERLOAD TRIP will be active
after Run LED is Lit.
(Motor is at full voltage)
(4)
OVERLOAD TRIP will be active
after MAX. START TIME has
elapsed.
(4)
Notes:
(1) Setting the INITIAL VOLTAGE to lower than 10% is not practical for loaded motors.
(2) Refer to section 7.6.8 page 40. See PHASE LOSS protection and refer to the warning below.
(3) Refer to section 9 page 55. See O/C or WRONG CON protection.
(4) In order to avoid OVERLOAD TRIP in special cases (very high inertia loads), where at the end of the
acceleration process, although motor is at full voltage (Run LED is Lit) and the current does not reduce to
nominal, set WIDER SETTINGS to ENABLE causing the OVERLOAD TRIP to be active only after MAX.
START TIME has elapsed.
WARNING!
Operator’s
responsibility!
1. WIDER SETTINGS are for use in very special applications only!
Do not set WIDER SETTINGS to ENABLE unless RVS-DX is significantly larger
than the motor! When using WIDER SETTINGS for the RVS-DX you must be
extremely careful to avoid damaging the motor or RVS-DX.
2. Only cancel PHASE LOSS protection when the operator is sure that no real
phase loss exists and PHASE LOSS protection is activated. This situation can
occur in rare cases when there is no real fault but the RVS-DX recognizes
unusual behaviour like when THDV (Total Harmonic Distortion in Voltage) in the
network is high.
If this is a true case of PHASE LOSS then after cancelling PHASE LOSS
protection the motor will single phase and most likely be tripped by the over load
protection mechanism.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Solcon RVS-DX Series and is the answer not in the manual?

Solcon RVS-DX Series Specifications

General IconGeneral
BrandSolcon
ModelRVS-DX Series
CategoryController
LanguageEnglish

Related product manuals