46 • Control Keypad
________________________________________________________________________________________
7.6.12 138BStatistical Data – page 9
STATISTICAL DATA
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(refer to section 7.6.3 on page 27 for changing mode)
Display and default
values
Displays total energy drawn by the motor in KWH.
Reading available in RVS-DX58A and up.
Displays last starting time in seconds.
Starting time is the duration until motor’s current reaches
Displays last starting maximum starting current.
Displays Motor’s total run time.
Displays total number of starts.
Displays motor’s last trip cause.
Displays motor’s current when motor was tripped by the RVS-
Displays total number of trips.
Displays the motor’s trip history.
NO DATA
7.7
98BNon adjustable protection anf fault Resetting
7.7.1
139BPhase loss (and Under / Over Frequency)
Becomes operational when starter is energized and protects motor from single phasing. Trips the starter when
1 or 2 phases are missing for more than 1 sec.
Starter will also trip when frequency is less than 45 or greater than 65Hz.
Note:
Phase loss might not be detected in lightly loaded motors.