50 STARTING PROCEDURE
________________________________________________________________________________________
8.2 Standard starting procedure
Connect Control Supply. On LED will lit.
Review all parameters with Mode and Select keys Set parameters as
required.
If necessary, return to Default Parameters (see “Service Mode”).
Connect mains voltage to starter’s line terminals.
Set LCD to show “MOTOR FLA” (% of motor FLA).
A l S d
Motor starts to turn
shortly after Start
Initial inrush current or
mechanical shock is
too high?
Increase “Initial Voltage” and start again
Decrease “Initial Voltage” and start again
Speed accelerates
smoothly to nominal?
Apply Stop command and wait until motor
stops.
Slightly increase Initial Voltage and Current Limit settings to allow for load
changes.
Current during
acceleration is too
high?
Decrease “Current Limit”
Motor speed
accelerate to nominal?
Increase “Current Limit”
Yes
No
Yes
No
No
Yes
Yes
No
No
Yes
A