EasyManua.ls Logo

Solcon RVS-DX Series - 4.3.8.2 RS-485 Communication (option # 3 M); 4.3.9 Inside-Delta mode; 4.3.9.1 General information

Solcon RVS-DX Series
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 Recommended Wiring Scheme
________________________________________________________________________________________
For thermistor input programming refer to section 7.6.8 on page 40.
Ground Terminal (terminal Gnd)
Connect thermistor and / or Analogue output shield to this ground terminal.
Analogue Output ( terminals Out (+), Out (-))
Dip switches allow selection between: 0-10VDC, 0-20mA, 4-20mA
Analogue value can be programmed via the key pad in I/O PROGRAMMING PARAMETERS page to
one of the values as follows: (refer to section
7.6.9 on page 42.)
A. 0….200% of FLA (Default setting)
B. 0….200% of Pn
C. Power factor (POWER FACTOR & POWER measurement only available in RVS-DX58A and up)
Dip No.
4-20 mA*
0-20 mA
0-10VDC
Dip-Sw. S1 # 1
On
On
Off
Dip-Sw. S1 # 2
On
On
Off
Dip-Sw. S1 # 3
Off
Off
On
Dip-Sw. S1 # 4
Off
Off
On
Dip-Sw. S2 # 1
On
Off
Off
Dip-Sw. S2 # 2
No use
No use
No use
* Default
Notes:
It is important that the RVS-DX is properly grounded, and control module is tightly fastened to the
power section.
Use twisted shielded cable for thermistor connection.
4.3.8.2 RS-485 Communication (option # 3M) (terminals out(-),Out(+))
Standard RS485, Half Duplex with MODBUS Protocol, baud rate 1200, 2400, 4800, 9600 BPS.
Twisted shielded pair should be used, connect shield to ground a PLC/Computer side.Terminals (-) & (+)
must be wired to control supply for operation in communication mode. Leave terminal NC not connected.
Note: When DeviceNet option is required an external device will be provided with the option.
This gateway is connected via 2 wires to the optional Modbus terminals.
Refer to section 7.6.10 on page 44.
4.3.9 “Inside-Delta” mode
4.3.9.1 General information
When the RVS-DX is installed “Inside Delta”, the individual phases of the Starter are connected in series
with the individual motor windings (6 conductor connections as with the star-delta starter). The soft
starter must only conduct about 67 % (=1\1.5) of the rated motor current. This ensures the use of a
significantly smaller device.
For example:
For a motor with a rated current of 155A motor, a 170A starter will be selected to operate “In-Line”.
For “Inside Delta” starter, we calculate (155 x 67% = 104A) and select a 105A starter.
Less heat dissipates in the cabinet vs. the standard “In-Line” connection.

Table of Contents

Related product manuals