OPERATING MANUAL MIC-2 ver. 1.8
9
Comments
- The AUTO-OFF countdown starts anew each
time the resistance is modified by at least 200Ω.
Additional information displayed by the
meter
and a
continuous
double
tone sonic
signal
The measured object is under a volt-
age exceeding +7V, lower than -1V
(with regard to R
ISO
-) or exceeding 5V
AC. The measurement is blocked.
Disconnect the meter from the ob-
ject (both terminals) immediately.
The measurement range has been ex-
ceeded.
2.3 Voltage measurements
The meter measures the voltage if the U
ISO
voltages have been selected (without pressing the
START button).
Additional information displayed by the
meter
or or
and a con-
tinuous double
tone sonic signal
The measured object is under
a voltage exceeding 600V
(positive, negative or alter-
nate). Disconnect the meter
from the object (both termi-
nals) immediately.