Connection resistance measurement
Continuous sonic signal for R < 10Ω
Insulation resistance measurement
Measurement voltages: 250V and 500V
Voltage accuracy
(R
obc
[] 1000*U
N
[V]): -0+10% of the select-
ed value
Temperature stability of voltage better than:
0.1% / °C
U
ISO
= 250V
Measurement range in accordance with
IEC 61557-2: 250k…1000M
U
ISO
= 500V
Measurement range in accordance with
IEC 61557-2: 500k…1999M
Other technical data
a) Type of insulation: double, in accordance with
EN 61010-1 and IEC 61557
b) Measurement category: IV 600V in accordance
with EN 61010-1
c) Protection class of the casing in accordance
with EN 60529: IP65
d) Maximum measurement current R
ISO
: 1,2mA ±
0,2mA
e) Maximum interference voltage at which a
measurement is realised R
ISO
: 20V
f) Measurement current R
CONT
(with closed termi-
nals for U
BAT
3,0V): < 10mA
g) Maximum voltage on open terminals for R
CONT
:
4…24V
h) Maximum interference voltage at which a
measurement is realised R
CONT
: +7V/-1V d.c.,
5V a.c.