35
Instruction for Use | HCA 56x and 8x8
After readout of the data from the radio heat cost allocator, the radio availability is deactivated again.
6.11.4 Operation Mode for Radio wM-Bus (868)
6.11.4.1 Readout over the short telegram (OMS compliant)
With this operating mode, the heat cost allocator Sontex 868 Radio transmits data:
Transmission interval each 120 seconds (minimum).
Radio reading, 24h/24h.
6.11.4.2 Readout over the long telegram for Walk-by reading
With this operating mode, the heat cost allocator Sontex 868 Radio transmits data:
Transmission interval each 120 seconds (minimum).
Radio reading and periods, 12h per day (programmable), 7days/7days.
6.11.4.3 Short or Long telegram Radio wM-Bus (868)
The choice of the telegram is done when ordering. It is not possible to select the telegram type
on the device itself..
6.11.5 Operation Mode Radio LoRaWAN® (878)
Depending on the quality of the network reception, the heating cost allocator automatically
determines whether a short or long telegram is sent. The transmission intervals correspond to
the values programmed into the device.
The reception quality of the network will automatically determine the choice
between a short or long telegram.
Time Device N° Time Device N°
20:00 - 20:59 xxxxxxx0 01:00 - 01:59 xxxxxxx5
21:00 - 21:59 xxxxxxx1 02:00 - 02:59 xxxxxxx6
22:00 - 22:59 xxxxxxx2 03:00 - 03:59 xxxxxxx7
23:00 - 23:59 xxxxxxx3 04:00 - 04:59 xxxxxxx8
00:00 - 00:59 xxxxxxx4 05:00 - 05:59 xxxxxxx9