5.21 - Thermostat times
Set the desired periods of time when the thermostat should be active. 2 periods can
be set per day, settings can also be copied to other days. Outside the set times the
thermostat is switched off.
Setting range: from 00:00 to 23:59 /default setting: 06:00 to 22:00
Party Funktion (Thermostat only)
With the party function the storage tem-
perature is heated up once to the
reference temperature (Tref off), disre-
garding the set thermostat times.
The party mode is enabled by pressing
the „esc“-key for 3 seconds in the main
menu. While this mode is active, the sys-
tem heats up to the reference “Tref Off,
regardless of preset thermostat times.
The mode is ended once the required
temperature is reached.
5.22 - Tmax S3
Switch-off temperature at sensor 3
If this value is exceeded at sensor 3 and the other conditions are also met, then the
controller switches the relay off. If sensor 3 falls below this value again and the other
conditions are also met, then the controller switches the relay on again.
Setting range: from 0°C to 99°C
Default setting: 60°C (in systems not using S3: Default Off)
Danger
Temperature values which are set too high can lead to scalding or dam-
age to the system. Scalding protection must be provided by the cus-
tomer!