In hydraulic systems with solar when the recooling function is activated excess energy
from the storage tank is fed back into the collector. This only takes place if the temper-
ature in the storage tank is higher than the value “Recool Tsetpoint” and the collector
is at least 20°C cooler than the storage tank and until the storage tank temperature
has dropped below the value “Recool Tsetpoint.
Recooling settings range: on / off / Default: off
Recooling Tset settings range: 0°C to 99°C / Default: 70°C
Caution
This function causes energy to be lost via the collector! The
recooling should only be activated in exceptional cases.
6.6. - Recooling (solar only)