Version: 1
Revision Date: 02/2018
N
2-BLAST
®
FPS-500
O&M Manual
Page: 16 of 25
Contact us Toll-Free: (888) 526-6284
6.1.6 Automatic Cut-In and Cut-Out
The generator starts and stops based on a pressure switch. Do not adjust the factory preset cut-
in and out pressure without rst consulting with South-Tek Systems.
6.1.7 Patented BlastOff
®
– Leak Detection System
The “BlastOff
®
Leak Detection” is a patented feature which sends an alarm if it detects a possible
gas leak. The alarm signal can be an audible, visual, and dry contact connection to the “Building
Management System’s (BMS)”. Power cycle the unit to reset the alarm, but avoid doing this
multiple times, without nding the cause, as it will shorten the generator’s life.
6.2 SPECIFICATIONS
N2-BLAST
®
FPS-500 – Specications
Nitrogen Purity 98.5+%
Installation Wall Mounted (Optional floor mounting kit available)
Display Hours/Power on/Operating
N2 Storage Pressure 60-70 PSIG
Cabinet Port Connections 1/2” NPT Female
Electrical 110-220V / 50-60Hz / 1Phase; 20 Amp Breaker
Compressor Integral / Oil-Free
Ambient Temperature 40° to 100°F
Noise Level (dbA) < 90 dbA
Size 12.75” W x 12” D x 27” H (Cabinet Dimensions)
Weight 84 lbs
Table 1: FPS-500 Nitrogen Generator Specications