Faults
04/2019 EN 33
Fault: Pump is loud
Possible cause Solution
Pump and pipes not
completely ventilated or
filled.
Ventilate pump.
Fill pump.
Suction height too
large/Unit’s NPSH
(intake) too low.
Correct the fluid level.
Install pump lower.
Completely open shut-off valve
in the intake.
If the resistance is too large,
modify the intake
line.
Check suction basket/suction
opening.
Observe the permitted pressure
reduct
ion speed.
Wear of components. Replace components.
Dynamic head lower than
that indicated in the
order.
Set operating point exactly.
For constant overload turn
the
impeller (further enquiry
required).
Pump strained or
vibrations in the pipes.
Check pipe connections and
pump fasteners, if necessary
reduce the pipe bracket
spac
ing.
Fasten pipes using
vibration
reducing materials.
Imbalanced rotor. Clean pump and pump parts.
Pump and/or motor
bearings are damaged.
Replace bearing.
Flow rate too low. Increase minimum flow rate.