IM-P403-88 AB Issue 5
27
6.2 Commissioning - Quick set-up
This section allows the user to carry out the minimum commissioning necessary to operate
the system.
It accepts the defaults set in the factory, so will only work if the original default settings have
not been altered. See default settings in Section 10, Technical information, to confirm.
Settings can then be tailored to suit the individual requirements of the customer / application
if required.
WARNING:
It is essential that you comply with National / local regulations and Guidance notes,
and the boiler manufacturers recommendations. It is imperative that the settings
you have accepted will allow the boiler to operate in a safe manner.
This procedure assumes a Pt100 is fitted to the controller.
Parameter Action
Set Point
Set to the TDS to the level at which the blowdown valve is to open and
press the
OK
button.
Alarm
Set to the TDS to the level at which the alarm is to operate and
press the
OK
button (must be higher than SP).
Cal
Set to the actual measured value of the TDS and
press the
OK
button.
Test the system to ensure that it is working correctly.