6. Commissioning
6.1 General information
All commissioning for the product is carried out via the front panel.
WARNING:
On entering the commissioning mode the product will cease normal control. The
control relay will shut the valve. For safety, the alarm relay will continue to operate as
normal. To regain normal control, return to the run menu by selecting 'end'.
Note: If the purge time has been reset, a new purge interval will begin.
If during commissioning, the buttons are not pressed for over 5 minutes, the controller
will revert to run mode and an error will be displayed. If the commissioning was
incomplete the controller may not provide the correct control.
The product has no battery. The programmed settings are held in non-volatile memory (Flash)
and are written to after changing a parameter and pressing the
OK
button.
Fig. 16
BC3150
x1000
x100
x10
OK
AL
CLN
Manually open valve
Scroll up the menu and
increase digits
Start probe clean function
Test the alarm
Enter commissioning
mode (five seconds) and
select parameters / digits
(when flashing)
LCD display