What causes Low Pressure Alarm on SPX HPD during drying?
- MMelissa MorganNov 24, 2025
A Low Pressure Alarm during drying in your SPX Dehumidifier may occur due to: * **Loss of dryer air supply:** Check the compressor that supplies the dryer. * **Excessive air demand:** Inspect the equipment downstream of the dryer. * **Faulty drying tower pressure switch:** Check the pressure switch operation using the tower pressure gauge for comparison, and replace the switch if it's defective. * **Drying tower Inlet Valve failure:** Check for loss of pilot air. Make sure the manual drain valve on the bottom of the pilot air filter is fully closed, the pilot air filter cartridge isn't clogged, and the pilot air shut-off valve is open. * **Drying tower Purge Exhaust Valve failure:** Check for airflow out of the drying tower Purge Valve or exhaust piping, indicating the valve isn...