Stamford PFC3 - Technical Specification

Stamford PFC3
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 8
TECHNICAL SPECIFICATION
Input voltage (50-60Hz) 115 range 110-125v ac Applies to PFC E000 - 22090 (GREEN)
220 range 200-230v ac 5VA
240 range 231-250v ac
277 range 251-290v ac (60 Hz only)
Input current PF/VAR sensing 5A CT 2.5VA
Current Limit 330mA CT 2.5VA
Voltage matching input 110v ac ± 10%
5 vA nominal
Low excitation limit input 150 V dc Max
AVR control range (A1 A2) ± 3 volts dc
Power Factor setting range (PF) 0.7 lag to 0.7 lead (see note 1)
Remote PF setting potentiometer value 10K ohms 1 watt
Reactive current setting range (VAR) generate/absorb 0-100% gen. current (see note 1)
Low excitation limit range 2-8 volts dc
Current limit range 70-100% gen. current
Control accuracy VAR ± 5% (see note 2)
Power Factor ± 0.05 pf
Voltage matching ± 2%
Reponse time constant 4 seconds
Generator output voltage limiting range ± 5% to ± 15%
Environmental Vibration 20-100 Hz 50 mm/s
100-2 kHz 3.3 g
Relative humidity 0-60 °C 95%
Operating temperature -40 to +70 °C
Storage temperature -55 to +80 °C
Note 1: Refer to generator lag/lead performance data sheets for permissible operating conditions.
Note 2: Control accuracy may drift if the CT secondary current falls below 0.5 Amps.