Fig.7
11
FLUE OPTIONS
TOP FLUE - UP & OUT
This type of flue configuration should comply with
the following (see Fig 7):
* The horizontal flue run can not exceed the
vertical flue rise.
* Minimum vertical flue rise of 0.5 metres.
* Maximum vertical flue rise of 14.5 metres.
* Maximum horizontal flue run of 7.5 metres.
TOP FLUE - VERTICAL
This type of flue configuration should comply with
the following (see Fig 8):
* Minimum vertical flue rise of 0.5 metres (from
top of unit before bend fitting).
* Maximum vertical flue rise of 15 metres.
* Maximum vertical flue rise reduced by 0.25
metres for every 45 degree bend fitted.
* Length of Vertical flue rise must be twice the
length of Horizontal flue run/offset.
Part Code Description
34100610/9030 HORIZONTAL FLUE TERMINATION
KIT
34100654 VERTICAL FLUE TERMINATION KIT
37100438/9032 COMBUSTIBLE WALL KIT
34100405 950mm STRAIGHT PIPE
34100404 450mm STRAIGHT PIPE
34100403 250mm STRAIGHT PIPE
34100402 100mm STRAIGHT PIPE
34100441 90 DEGREE BEND
34100421 45 DEGREE BEND
45150169 FLAT ROOF FLASHING KIT
75000006 SLATE ROOF FLASHING KIT
45150173/9019 30-45 DEGREE TILE FLASHING KIT
STANLEY FLUE FITTINGS
The table below details the list of Waterford Stanley
Approved Flue Fittings for this stove.