AAP87600 PDU Specifications
System Specifications A-9
Table A- 4 lists the specifications for the AAP87600 PDUs.
Table A-4. AAP87600 PDU: Specifications
Power
Input power N/A
Nominal input voltage; frequency 200–240 VAC; 50/60 Hz
Physical Dimensions
Height 1.75 in. (4.45 cm)
Width 19.1 in. (48.51 cm)
Depth 6.75 in. (17.15 cm)
Environmental
Operating temperature during
operation
41
F to 95 F (5 C to 35 C)
For every 800 ft (243.8m) above 2000 ft (609.6m), lower
the maximum operating temperature (95
F (35 C)) by
1.8 F (1 C).
Maximum rate of temperature
change during operation
12
C per hour or 0.2 C per minute
Relative humidity during
operation
10% to 80% (noncondensing)
Storage temperature to 40,000 ft
(12.2 km)
-38
F to 140 F (-40 C to 60 C)
Relative humidity during storage 5% to 95% (noncondensing)