Studer Innotec SA
Quick guide RCC-02/-03
10 V 6.1.0 Quick guide
Level
Xtender parameter description
Factory value
Expert
1128
Transfer relay allowed
Yes
Expert
1580
Delay before closing transfer relay
0 min
Basic
1126
Smart-Boost allowed
Yes
Inst.
1607
Limitation of the power Boost
100%
Basic
1107
Maximum current of AC source (Input limit)
32 Aac
Expert
1471
Max input current modification
Expert
1566
Using a secondary value for the maximum current of
the AC source
No
Expert
1567
Second maximum current of the AC source (Input limit)
16 Aac
Expert
1527
Decrease max input limit current with AC-In voltage
No
Expert
1554
Decrease of the max. current of the source with input
voltage activated by remote entry
No
Expert
1309
AC input low limit voltage to allow charger function
180 Vac
Expert
1433
Adaptation range of the input current according to the
input voltage
10 Vac
Expert
1553
Speed of input limit increase
50
Expert
1295
Charge current decrease coef. at voltage limit to turn
back in inverter mode
100%
Expert
1436
Overrun AC source current limit without opening the
transfer relay (Input limit)
Yes
Basic
1552
Type of detection of the grid loss (AC-In)
Tolerant
Expert
1510
Tolerance on detection of AC-input loss (tolerant UPS mode)
100
Expert
1199
Input voltage giving an opening of the transfer relay with delay
200 Vac
Expert
1198
Time delay before opening of transfer relay
8 sec
Expert
1200
Input voltage giving an immediate opening of the transfer
relay (UPS)
180 Vac
Inst.
1432
Absolute max limit for input voltage
270 Vac
Expert
1505
Delta frequency allowed above the standard input frequency
5 Hz
Expert
1506
Delta frequency allowed under the standard input frequency
5 Hz
Expert
1507
Duration with frequency error before opening the transfer
2 sec
Expert
1575
AC-IN current active filtering (Not in parallel)
No
Inst.
1557
Use an energy quota on AC-input
No
Inst.
1559
AC-In energy quota
1 kWh
Expert
1201
AUXILIARY CONTACT 1
Expert
1202
Operating mode (AUX 1)
Automatic
Expert
1497
Combination of the events for the auxiliary contact (AUX 1)
Any (Function OR)
Expert
1203
Temporal restrictions (AUX 1)
Expert
1204
Program 1 (AUX 1)
Expert
1205
Day of the week (AUX 1)
None days
Expert
1206
Start hour (AUX 1)
07:00 hh:mm
Expert
1207
End hour (AUX 1)
20:00 hh:mm
Expert
1208
Program 2 (AUX 1)
Expert
1209
Day of the week (AUX 1)
None days
Expert
1210
Start hour (AUX 1)
07:00 hh:mm
Expert
1211
End hour (AUX 1)
20:00 hh:mm
Expert
1212
Program 3 (AUX 1)
Expert
1213
Day of the week (AUX 1)
None days
Expert
1214
Start hour (AUX 1)
07:00 hh:mm
Expert
1215
End hour (AUX 1)
20:00 hh:mm