Studer Innotec SA 2014 V4.4.0
4O9C
Remote control and programming unit
RCC-02
and
RCC-03
for the Xtender
User manual

Table of Contents

Other manuals for Studer RCC-02

Question and Answer IconNeed help?

Do you have a question about the Studer RCC-02 and is the answer not in the manual?

Studer RCC-02 Specifications

General IconGeneral
BrandStuder
ModelRCC-02
CategoryRemote Control
LanguageEnglish

Summary

Reference

FOREWORD

CONVENTIONS

Explains symbols, terminology, and warnings used in the manual.

PRODUCT RECYCLING

Provides information on product disposal and environmental compliance.

EC DECLARATION OF CONFORMITY

STUDER INNOTEC CONTACT DETAILS

YOUR RESELLER’ CONTACT DETAILS

WARNINGS AND CAUTION

WARRANTY

Details the warranty terms, coverage, and exclusions for the product.

LIMITATION OF RESPONSABILITY

Outlines the limitations of liability for the manufacturer.

SAFETY INSTRUCTIONS

Crucial precautions for safe operation and handling of the device.

ACCEPTANCE OF THE SOFTWARE LICENCE AND UPDATES

Terms and conditions for using the software and its updates.

COMPATIBILITY

ACCESS CODE FOR EXTENDED FUNCTIONS

INTRODUCTION

MODELS CONCERNED

Lists the Xtender models compatible with this remote control.

CONTROLS AND INDICATORS

Describes the function of buttons and the display on the remote control.

SD CARD

CONNECTION

SERIES CONNECTION

Explains how to connect multiple devices in a series network.

RCC-02

RCC-03

Xtender XTH

Xtender XTM

Xtender XTS

VarioString

VarioTrack

BSP

Xcom-232i

DIMENSIONS

RCC-02

Provides the physical dimensions for the RCC-02 unit.

RCC-03

Provides the physical dimensions for the RCC-03 unit.

QUICK START GUIDE

SETTING OF THE LANGUAGE

Step-by-step guide to setting the display language.

ADAPTATION TO THE SOURCE

Configures the unit to match the connected power source characteristics.

ADAPTATION TO THE BATTERY

ACTIVATION OF THE FUNCTION SMART-BOOST

BASIC DISPLAYS

ACTIVATING AND DEACTIVATING THE COMBI XTENDER

QUICK SETTING OF THE MAXIMUM SOURCE AC CURRENT

SETTING OF THE RCC REMOTE CONTROL

SETTING OF THE LANGUAGE {5000}

OTHER LANGUAGES {5036}

SETTING OF TIME {5001} AND DATE {5002}

USER LEVEL {5012}

DRIVE THE REMOTE CONTROL TO THE USER LEVEL BASIC {5019}

INSTALLER - MODIFICATION OF THE XTENDER PARAMETERS THRESHOLDS TOGETHER {5042}

Force all Xtender parameters to threshold {5043}

Sets all Xtender parameters to their defined threshold values.

Restore the default thresholds of the Xtender parameters {5044}

Restores the default threshold values for Xtender parameters.

DATA LOGGER {5057}

Data logger enabled {5101}

Enables or disables the automatic data logging function.

Backup of the current day data {5059}

Forces a backup of the data recorded for the current day.

BACKUP AND RESTORING {5013}

Backup of all files {5041} (System backup)

Performs a complete backup of system files including configurations.

Restore all files {5068} (System recovery)

Restores the system configuration from a saved backup file.

Apply configuration files (master file) {5070}

Separator of the csv files {5032}

Advanced backup functions {5069}

Messages backup {5030}

Saves message history files (event history) to the SD card.

Save and restore RCC files {5049}

Commands for saving and restoring files specific to the RCC remote control.

Save and restore Xtender files {5050}

Commands for saving and restoring files specific to Xtender inverter-chargers.

Loading an Xtender master file {5034}

Load Xtender parameters preset {5045}

INSTALLER - Formatting the SD card {5047}

Starting the update {5061}

ADJUSTING THE CONTRAST

BACK-LIGHTING {5007}

Backlight modes {5093}

Sets the backlight behavior: always on, off, or delayed.

Duration of the back-lighting {5009}

Determines how long the backlight stays active after inactivity.

Red back-lighting if the Xtender is OFF and if there is a fault {5026}

Configures red backlight to indicate an OFF state or fault.

EXTENDED AND SPECIAL FUNCTIONS {5021}

Choice of the display by default {5073}

Selects the default screen displayed upon menu exit or connection.

Inactivity period before returning to the standard display {5010}

Sets the time before the display reverts to the basic screen.

Duration of display for quick messages {5011}

Sets the display duration for less critical messages.

Acoustic alarm {5027}

Enables or disables audible alarms for system events.

Remote control acoustic alarm duration {5031}

Adjusts the duration of the acoustic alarm sound.

Switching on and off of system on level View only {5056}

Restricts ON/OFF control when the unit is in 'View Only' mode.

INFORMATION ON THE OPERATING MODE OF THE INSTALLATION

DISPLAY OF THE PARALLEL AND THREE-PHASE SYSTEMS

MESSAGES AND ACCOUNT OF EVENTS

(000) WARNING: BATTERY VOLTAGE LOW

Indicates a low battery voltage warning and its potential consequences.

(003) AC-IN SYNCHRONIZATION IN PROGRESS

Shows the status of the AC input synchronization process.

(004) INPUT FREQUENCY AC-IN WRONG

(006) INPUT VOLTAGE AC-IN TOO HIGH

(007) INPUT VOLTAGE AC-IN TOO LOW

(008) HALTED: INVERTER OVERLOAD SC

(014) HALTED: OVER TEMPERATURE EL

(015) HALTED: INVERTER OVERLOAD BL

(016) WARNING: FAN ERROR DETECTED

(018) WARNING: EXCESSIVE BATTERY VOLTAGE RIPPLE

(019) HALTED: BATTERY UNDER VOLTAGE

(020) HALTED: BATTERY OVERVOLTAGE

(021) INPUT LIMIT REACHED, NO TRANSFER

(022) ERROR: VOLTAGE PRESENCE ON AC-OUT

(023) ERROR: INVERTER PHASE NOT DEFINED

(024) CHECK THE CLOCK BATTERY

(041) WARNING: OVERTEMPERATURE TR

(042) HALTED: UNAUTHORIZED ENERGY SOURCE AT THE OUTPUT

(058) ERROR: SYNCHRONIZATION WITH MASTER LOST

(059) HALTED: INVERTER OVERLOAD HW

(060) (061) WARNING: TIME SECURITY FOR AUXILIARY CONTACTS

(062) WARNING: GENSET, NO AC-IN COMING AFTER AUX COMMAND

STORED EVENTS

DATA LOGGING

FUNCTIONING

Details how the data logger function operates and records system data.

ANALYSIS AND VISUALIZATION OF THE DATA WITH THE XTENDER DATA ANALYSIS TOOL

Explains how to use the analysis tool for CSV data interpretation.

SETTING OF THE XTENDER

GENERAL

Overview of basic Xtender configuration principles.

CONFIGURATION ON A SYSTEM WITH SEVERAL XTENDERS

Guidelines for configuring systems with multiple Xtender units.

UTILISATION AND ACCESS LEVELS

Describes user levels and their respective access permissions.

PRE-DEFINED FUNCTIONS OF THE AUXILIARY RELAYS

Information on factory pre-set functions for auxiliary relays.

ACCESS TO THE PARAMETERS

Access to a parameter by its number

Method for accessing and modifying parameters using their reference number.

Access to a parameter via the menu

Method for navigating and accessing parameters through the menu structure.

INSTALLER - UTILISATION AND ACCESS LEVELS

BASIC SETTINGS {1100}

Setting of the basic parameters by means of the potentiometer in the XTS {1551}

Configures basic parameters using the XTS potentiometer controls.

Maximum current of the AC source (Input limit) {1107}

Charge current {1138}

Smart boost authorized {1126}

Authorized inverter {1124}

Type of detection of the grid loss (AC-In) {1552}

Standby level {1187}

Restore default configurations {1395}

INSTALLER - Restore factory settings {1287}

MANAGEMENT AND BATTERY CYCLE {1137}

Authorized charger {1125}

Battery charge current {1138}

Temperature correction coefficient {1139}

Undervoltage {1568}

Level of battery undervoltage at no load {1108}

Sets the battery undervoltage level for deactivating inverter/Smart Boost.

Dynamic compensation of the batteries undervoltage {1531}

Dynamic battery undervoltage compensation {1191}

Enables dynamic adjustment of battery undervoltage disconnection voltage.

Type of dynamic compensation {1532}

Selects the type of dynamic compensation for battery undervoltage.

Low voltage disconnection at full-load {1109}

Duration of undervoltage before disconnection {1190}

Reactivation voltage after battery undervoltage {1110}

Adaptable low voltage disconnection (B.L.O) {1194}

Max voltage for adaptive low voltage {1195}

Reset voltage of the adaptable correction {1307}

Increment of the adaptative correction {1298}

Maximum operating voltage {1121}

Reactivation voltage after battery overvoltage {1122}

Battery maintenance voltage (floating) {1140}

Force passage to floating mode {1467}

New cycle {1141}

Force new cycle {1142}

Allows forcing the start of a new battery charge cycle.

Voltage 1 for a new cycle {1143} and duration at undervoltage 1 for a new cycle {1144}

Sets voltage and duration for the first new cycle condition.

Voltage 2 for a new cycle {1145} and duration at undervoltage 2 for a new cycle {1146}

Sets voltage and duration for the second new cycle condition.

New priority cycle on the absorption and equalization phases {1149}

Dynamic compensation of battery level for a new cycle {1608}

Restricted maximum cycle frequency {1147}

Minimum duration between cycles {1148}

Absorption phase {1451}

Authorized absorption {1155}

Enables or disables the battery absorption charging phase.

Absorption voltage {1156}

Sets the voltage level used during the absorption phase.

Duration of absorption {1157}

Sets the duration for the battery absorption charging phase.

Completion of absorption released by the current {1158}

Current at end of absorption {1159}

Control of the maximum frequency of the absorptions {1160}

Minimum duration since the last absorption {1161}

Equalization phase {1452}

Authorized equalization {1163}

Enables or disables the battery equalization charging phase.

Force an equalization {1162}

Allows forcing the start of a battery equalization phase.

Equalization before absorption phase {1291}

Equalization current {1290}

Equalization voltage {1164}

Duration of equalization {1165}

Number of cycles prior to equalization {1166}

Equalization with fixed interval {1284}

Weeks between equalizations {1285}

End of equalization activated by the current {1168}

Current threshold to end equalization phase {1169}

Reduced floating phase {1453}

Authorized reduced floating phase {1170}

Enables the reduced floating phase for lower water consumption.

Duration of floating before reduced floating {1171}

Sets the duration of the floating phase before reduced floating.

Voltage of reduced floating {1172}

Sets the voltage level for the reduced floating phase.

Periodic absorption phase {1454}

Authorized periodic absorption {1173}

Periodic absorption voltage {1174}

Duration of reduced floating before periodic absorption {1175}

Duration of periodic absorption {1176}

INVERTER {1186}

Authorized inverter {1124}

Authorizes the operation of the inverter function.

Output voltage {1286}

Allows adjustment of the inverter's output voltage.

Increase of the linear AC-Out voltage with the battery voltage {1548}

Maximum increase of the AC-Out voltage by the battery voltage {1560}

Frequency {1112}

Increase of the frequency at full battery {1536}

Frequency increase with the battery voltage {1549}

Maximum increase of the frequency {1546}

Speed of the change output voltage/frequency according to the battery voltage {1534}

Standby and start (load detection) {1420}

Standby level {1187}

Sets the power level at which the inverter enters standby mode.

Duration between the standby pulses {1189}

Determines the interval between standby pulses for load detection.

Number of standby periods {1188}

Sets the number of periods generated during a standby burst.

Duration of Softstart {1599}

Solsafe presence, energy source at AC-Out side {1438}

AC-IN AND TRANSFER {1197}

Authorized transfer {1128}

Authorizes or prohibits the operation of the transfer relay.

Delay before closing of the transfer relay {1580}

Sets a delay before the transfer relay closes, even if AC-In voltage is present.

Smart-Boost authorized {1126}

Authorizes the Smart-Boost function to supplement power from batteries.

Limitation of the Smart-boost power {1607}

Limits the maximum power provided by the Smart-Boost function.

Maximum current of the AC source (Input limit) {1107}

Adaptation of the input current {1471}

Using a secondary value for the maximum current of the AC source {1566}

Allows using a secondary value for AC source current limit.

Second maximum current of the AC source {1567}

Sets a second maximum current value used when command entry is active.

Decrease of the max. current of the source with input voltage {1554}

Decreases max source current based on input voltage when command entry is active.

AC-In minimum voltage to decrease the input current {1309}

Input voltage range for adjusting the input current {1433}

Adjustment coefficient in between the input current and the minimum input voltage {1295}

Authorization to exceeding the maximum current of the source (Input limit) without interrupting the transfer {1436}

Type of detection of the grid loss (AC-In) {1552}

Sensitiveness of the detection « tolerating » of grid loss (AC-In) {1510}

Transfer AC-In for delayed transfer opening {1199}

Delay before passing to inverter {1198}

Immediate transfer AC-In voltage {1200}

INSTALLER – Absolute maximum input voltage {1432}

Delta frequency allowed above the standard input frequency {1505}

Delta frequency allowed below the standard input frequency {1506}

Duration of erroneous frequency before disconnecting the transfer relay {1507}

AC-In current active filtering {1575}

INSTALLER - Use an energy quota on AC-input {1557}

INSTALLER - AC-In Energy Quotas {1559}

CONFIGURATION OF AUXILIARY CONTACTS 1 AND 2 {1201} {1310}

Switching mode {1202} {1311}

Combination of events mode {1497} {1498}

Temporal restrictions {1203} {1312}

Contacts activated with set schedules {1269} {1378}

Contacts activated by an event {1455} {1456}

Xtender OFF {1225} {1333}

Xtender ON {1518} {1519}

Remote ON/OFF input active {1543} {1544}

Battery undervoltage alarm {1226} {1334}

Battery overvoltage {1227} {1335}

Inverter or smart boost overload {1228} {1336}

Overtemperature {1229} {1337}

No overtemperature alarm {1520} {1521}

Active charger {1231} {1339}

Active inverter {1232} {1340}

Smart-Boost active {1233} {1341}

AC-In present with fault {1234} {1342}

AC-In present {1235} {1343}

Transfer relay drawn {1236} {1344}

AC-Out present {1237} {1345}

Battery charging in bulk charge phase {1238} {1346}

Battery charging in absorption phase {1239} {1347}

Battery charging in equalization phase {1240} {1348}

Battery charging in floating phase {1242} {1350}

Battery charging in reduced floating phase {1243} {1351} and

Battery charging in periodic absorption phase {1244} {1352}

INSTALLER - Quota AC-In active {1601} {1602}

Contacts activated by the battery voltage {1245} {1353}

Dynamic compensation of the thresholds {1288} {1354}

Deactivate if the battery is in floating mode {1516} {1517}

Contacts activated by inverter power or Smart-Boost {1257} {1366}

Contacts activated on battery state of charge (SOC) {1501} {1502}

Security: Limit the time of activation {1512} {1513}

Maximum duration of activation {1514} {1515}

Reset all settings {1569} {1570}

AUXILIARY CONTACTS 1 AND 2 EXTENDED FUNCTIONS {1489}

Generator startup

Configures generator startup sequence using auxiliary contacts.

Generator control {1491}

Manages the generator start impulses and sequence.

Number of starting attempts {1493}

Sets the maximum number of generator start attempts.

Starter pulse (with AUX2) {1492}

Adjusts the timing of the starter pulse activation.

Time before a starter pulse {1494}

Sets the time delay before a starter pulse or restart.

Main contact hold/interrupt time {1574}

Sets the hold/interrupt time for the main contact during cranking.

SYSTEM {1101}

Command entry {1537}

Customizes various settings related to the command entry input.

Activated by the state AUX1 {1578}

Forbids the battery as priority source {1579}

INSTALLER - Deactivating the minigrid mode {1600}

Battery as priority energy source {1296}

Votage of the battery priority {1297}

Duration of the acoustic alarm {1565}

Automatic restart {1129}

Delay to restart after an overload {1533}

Sets the delay before the unit attempts to restart after an overload.

Auto-start when switched on {1111}

Ground/neutral system {1484}

Ground relay prohibited {1485}

Prohibits the connection between neutral and ground.

Neutral always connected {1486}

Ensures the AC-out neutral remains connected to the AC-in neutral.

INSTALLER – Watchdog control system {1628} and {1629}

INSTALLER – Flash saving of the parameter {1550}

Reset of all inverters {1468}

MULTI XTENDER {1282}

3-phase integral mode {1283}

Multiple authorized inverters {1461}

Multiple independent inverters {1462}

Battery cycle synchronized by the master {1555}

Authorize the stand-by of the secondary inverters (slaves) {1547}

Splitphase: L2 with 180 degrees phase displacement {1571}

INSTALLER – Compatible Minigrid {1437}

INSTALLER – Minigrid with battery energy sharing {1577}

GRID-FEEDING {1522}

Grid-feeding authorized {1127}

Authorizes or prohibits the grid-feeding function.

Maximum grid-feeding current {1523}

Sets the limit for the grid-feeding current.

Forced grid-feeding {1524} {1525} {1526}

INSTALLER - Dephased injection {1610}

INSTALLER - Cos phi at P=0% {1622}

INSTALLER - Cos phi at a given power. Cos phi {1623}, P= {1613}

INSTALLER - Cos phi at P=100% {1624}

INFORMATION ON THE SYSTEM

REMOTE CONTROLS

Information on hardware and software versions of remote controls.

XTENDER

Information on connected Xtender units and their versions.

SOFTWARE(S) UPDATING

UPDATING PROCESS

Step-by-step guide for updating the system software.

APPLICATION EXAMPLES

GENERAL USE: INVERTER, CHARGER WITH GRID

Illustrates a standard setup with grid connection and basic functions.

USE OF A LIMITED POWER SOURCE

Example of using limited power sources like generators or dock connections.

USE TO INCREASE THE POWER ON AN EXISTING INSTALLATION

LOAD SHEDDING OF THE SECOND PRIORITY LOADS

APPENDICES

APPENDIX 1: LIST OF CONFIGURATION INTERDEPENDENCIES

A table detailing dependencies between various configuration parameters.

PARAMETER TABLES

REMOTE CONTROL PARAMETERS

Reference table listing parameters for the RCC remote control.

INVERTER PARAMETERS

PARAMETER INDEX {XXXX}