Studer Innotec SA
RCC-02/-03
User manual V4.4.0 47
14.8.4.7 Reset voltage of the adaptable correction {1307}
The battery undervoltage threshold returns to its original value if the battery reaches the voltage
determined by this threshold.
14.8.4.8 Increment of the adaptative correction {1298}
At each shut down by undervoltage, the shut down threshold is increased by this value.
14.8.5 Maximum operating voltage {1121}
This setting allows you to adjust the maximum battery voltage for operation in inverter mode.
14.8.6 Reactivation voltage after battery overvoltage {1122}
In case of a battery overvoltage, the battery has to return to a voltage lower than the value fixed by
this setting in order to unlock inverter operation. If the auto-restart after overvoltage function is
activated, the Xtender will automatically restart once the battery voltage has gone beneath this
value.
14.8.7 Battery maintenance voltage (floating) {1140}
Use this configuration to adjust the voltage that will be used when the battery is completely charged.
This voltage prevents automatic discharging and maintains the battery at its maximum level of
charge.
14.8.8 Force passage to floating mode {1467}
This configuration may be used to force a battery cycle in progress and to bring it to the end of
charge values. If the battery voltage level is higher, the charger is temporarily disconnected. If the
battery level is lower, the charging current is increased up to the maximum in order to reach the set
level as quickly as possible.
14.8.9 New cycle {1141}
Battery charging is a complex function that generally ends with a maintenance phase (floating) of
indeterminate duration. The configurations below allow adjustment of the conditions that lead to the
starting of a new charge cycle.
14.8.9.1 Force new cycle {1142}
This configuration allows a new charge cycle to be forced, and the bulk phase follows straight away.
Voltage 1 for a new cycle {1143} and duration at undervoltage 1 for a new cycle {1144}
Voltage 2 for a new cycle {1145} and duration at undervoltage 2 for a new cycle {1146}
The battery voltage value, below which a new cycle is started, can be specified. The battery voltage
must remain below this threshold for the duration that is also to be determined. Two voltages
associated with two durations are configurable. Generally, a higher voltage is used with a longer
duration and a lower voltage with a shorter duration.