Studer Innotec SA
RCC-02/-03
User manual V4.4.0 65
Voltage for deactivation of the auxiliary contact {1255} {1364}
Duration over battery voltage for deactivation {1256} {1365}
Deactivate if the battery is in floating mode {1516} {1517}
14.11.6.1 Dynamic compensation of the thresholds {1288} {1354}
If the contacts are activated according to the battery voltage, you can use the voltage dynamically
compensated for each threshold.
If this function is not activated, the average battery voltage will be used.
If this function is activated, the real battery voltage is compensated according the power used.
14.11.6.2 Deactivate if the battery is in floating mode {1516} {1517}
If you activate one of the auxiliary contacts according to the battery voltage, you can force the
deactivation if the battery is in floating mode. In this way, even if the deactivation voltage is not
reached or if the duration of the voltage deactivation is not completed, the auxiliary contact will be
released.
14.11.7 Contacts activated by inverter power or Smart-Boost {1257} {1366}
If the power output of the inverter exceeds a certain level, the contact may be activated. The excess
is linked to a duration. Three power levels linked to three durations are configurable to activate the
auxiliary contact.
The auxiliary contact will only be activated after the output power passes below a value and over a
duration, both independently of the activation configurations.
If the Smart-Boost function is active, these configurations are also taken into account with the power
of the boost.
Power 1 active {1258} {1367}
Power 1 {1259} {1368}
Duration 1 {1260} {1369}
Power 2 active {1261} {1370}
Power 2 {1262} {1371}
Duration 2 {1263} {1372}
Power 3 active {1264} {1373}
Power 3 {1265} {1374}
Duration 3 {1266} {1375}
Power for deactivation of the auxiliary contact {1267} {1376}
Duration below power for deactivation {1268} {1377}
14.11.8 INSTALLER - Contacts activated according to the battery
temperature {1503} {1504}
You can activate an auxiliary contact according to the battery temperature. This function is
available with the temperature sensor BTS-01 or with the battery monitor BSP. Two distinct thresholds
allow a switch on and off of the contact at different temperatures.
Contact active with the battery temperature {1446} {1457}
Auxiliary contact activated below {1447} {1458}
Auxiliary contact deactivated below {1448} {1459}