Studer Innotec SA
Quick guide RCC-02/-03
12 V 6.1.0 Quick guide
Level
Xtender parameter description
Factory value
Expert
1248
Delay 1 (AUX 1)
1 min
Expert
1249
Battery voltage 2 activate (AUX 1)
Yes
Expert
1250
Battery voltage 2 (AUX 1)
11.9/23.9/47.8 Vdc
Expert
1251
Delay 2 (AUX 1)
10 min
Expert
1252
Battery voltage 3 activate (AUX 1)
Yes
Expert
1253
Battery voltage 3 (AUX 1)
12.1/24.2/48.5 Vdc
Expert
1254
Delay 3 (AUX 1)
60 min
Expert
1255
Battery voltage to deactivate (AUX 1)
13.5/27/54 Vdc
Expert
1256
Delay to deactivate (AUX 1)
60 min
Expert
1516
Deactivate if battery in floating phase (AUX 1)
Yes
Expert
1257
Contact active with inverter power or Smart-Boost (AUX 1)
Expert
1258
Inverter power level 1 activate (AUX 1)
No
Expert
1259
Power level 1 (AUX 1)
120 % Pnom
Expert
1260
Time delay 1 (AUX 1)
1 min
Expert
1261
Inverter power level 2 activate (AUX 1)
No
Expert
1262
Power level 2 (AUX 1)
80 % Pnom
Expert
1263
Time delay 2 (AUX 1)
5 min
Expert
1264
Inverter power level 3 activate (AUX 1)
No
Expert
1265
Power level 3 (AUX 1)
50 % Pnom
Expert
1266
Time delay 3 (AUX 1)
30 min
Expert
1267
Inverter power level to deactivate (AUX 1)
40 % Pnom
Expert
1268
Time delay to deactivate (AUX 1)
5 min
Inst.
1503
Contact active according to battery temperature (AUX 1)
With BSP or BTS
Inst.
1446
Contact activated with the temperature of battery
(AUX 1)
No
Inst.
1447
Contact activated over (AUX 1)
3 °C
Inst.
1448
Contact deactivated below (AUX 1)
5 °C
Expert
1501
Contact active according to SOC (AUX 1) Only with BSP
Expert
1439
Contact activated with the SOC 1 of battery (AUX 1)
No
Expert
1440
Contact activated below SOC 1 (AUX 1)
50 % SOC
Expert
1581
Delay 1 (AUX 1)
12 hours
Expert
1582
Contact activated with the SOC 2 of battery (AUX 1)
No
Expert
1583
Contact activated below SOC 2 (AUX 1)
30 % SOC
Expert
1584
Delay 2 (AUX 1)
0.2 hours
Expert
1585
Contact activated with the SOC 3 of battery (AUX 1)
No
Expert
1586
Contact activated below SOC 3 (AUX 1)
20 % SOC
Expert
1587
Delay 3 (AUX 1)
0 hours
Expert
1441
Contact deactivated over SOC (AUX 1)
90 % SOC
Expert
1588
Delay to deactivate (AUX 1)
0.2 hours
Expert
1589
Deactivate if battery in floating phase (AUX 1)
Yes
Expert
1512
Security, maximum time of contact (AUX 1)
No
Expert
1514
Maximum time of operation of contact (AUX 1)
600 min
Expert
1569
Reset all settings (AUX 1)
-
Expert
1310
AUXILIARY CONTACT 2
Expert
1311
Operating mode (AUX 2)
Reversed
automatic
Expert
1498
Combination of the events for the auxiliary contact (AUX 2)
Any (Function OR)
Expert
1312
Temporal restrictions (AUX 2)