EasyManua.ls Logo

Studer Xtender Series - BTS-01 Temperature Sensor

Studer Xtender Series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
STUDER Innotec
Xtender
28 V.3.2.0 User manual
The two remote control models are delivered with a 2 m cable by default.
Cables of specific lengths (5 m, 20 m and 50 m) can be ordered.
The article no. is as follows: CAB-RJ45-xx. The length in metres is specified as xx
Up to 3 RCC-02/03 remote controls can be connected in series on the communication bus of one
Xtender or an Xtender multi-inverter system. In a system comprising a single Xtender, the
connection of the RCC-02 or RCC-03 may be conducted without stopping the Xtender (warm).
When connecting an RCC-02/03 remote control in a multi-unit system, it is recommended that all
units in the system be stopped and that the communication bus on the device on which the
connection is being made be terminated.
The 2 switches for the communication bus termination, “Com. Bus" (4) both remain in
position T (terminated) except when both
connectors are in use. In this case, and only in
this case, both must be placed in the O open position. If one of the two connectors is not
in use, the two termination switches (14) will be in position T.
6.4.2
BTS-01 temperature sensor
The optimal operating voltages for lead batteries vary depending on the
temperature. A temperature sensor is optionally available to correct the
battery voltage and guarantee an optimum charge whatever the battery
temperature. The correction factor given by the correction of the sensor is
set by the configuration {1139}
Article no. for the temperature sensor (including a cable of 3 m): BTS-01.
Dimensions: H x W x D / / 58 x 51.5 x 22 mm

Table of Contents