19 TECHNICAL DATA – XTM
XTM model 1500-12 2000-12 2400-24 3500-24 2600-48 4000-48
Inverter
Rated battery voltage 12V 24V 48V
Input voltage range 9.5 - 17V 19 - 34V 38 - 68V
Continuous power @ 25 °C 1500VA 2000 VA 2000VA 3000 VA 2000VA 3500 VA
Smart Boost power 1500VA 2000 VA 2400VA 3500 VA 2600VA 4000 VA
30 minute load @ 25 °C 1500VA 2000 VA 2400VA 3500 VA 2600VA 4000 VA
5 second load @ 25 °C 3 x Pcont.
Maximum load Up to short-circuit
Maximum asymmetrical load Up to Pnom
Load detection (standby) 2 to 25W
Admissible cos phi 0.1 - 1
Maximum efficiency 93% 94% 96%
Idle power OFF/standby/ON
1.2W/
1.4W/8W
1.2W/
1.4W/10W
1.4W/
1.6W/
9W
1.4W/
1.6W/
12W
1.8W/2W
/10W
1.8W/2.1W/
14W
Output voltage
Sin wave 230Vac (+/-2%) / 180-245 Vac or
****Sin wave 120 Vac (+/-2%) / 50-140 Vac
Output frequency
50 Hz adjustable 45-65 Hz +/- 0.05% (quartz-controlled)
****60 Hz adjustable 45-65 Hz +/- 0.05% (quartz-controlled)
Harmonic distortion <2%
Overcharge and short-circuit Automatic disconnection then 2 startup attempts
Overheating protection Alarm prior to disconnection and automatic restart
Battery charger
6-phase battery charger Programmable I-U-Uo-equalisation-Uo(low)-U(periodic)
Adjustable charge current 0 - 70A 0 - 100A 0 - 55A 0 - 90A 0 - 30A 0 - 50A
Input current limit 1 - 50A
Maximum input voltage 265Vac / ****150Vac
AC input voltage range
Level detection adjustable from 150 to 230 Vac
****Level detection adjustable from 50 to 140 Vac
Admissible input frequency 45 - 65Hz
(PFC) EN 61000-3-2
Battery control (factory value / adjustable range with RCC-02)
End of absorption by duration: 2h / 0.25 - 18 h or by current <10A / 2 - 50 A
Absorption voltage 14.4V/9.5-17V 28.8 / 19 - 34V 57.6 / 38 - 68V
Periodic absorption voltage - / 9.5 - 17V - / 19 - 34V - / 38 - 68V
Floating voltage 13.6V/9.5-17V 27.2 / 19 - 34V 54.4 / 38 - 68V
Reduced maintenance
voltage
- / 9.5 - 17V - / 19 - 34V - / 38 - 68V
Equalisation By number of cycles ( - / - 100) or at fixed intervals ( - / 52 weeks)
End of equalisation By duration 2h / 0.25 – 10h or by current - / 5 – 50 A
Equalisation voltage - / 9.5 - 17V - / 19 - 34V - / 38 - 68V
Low voltage disconnection 10.8V/9.5- 17V 21.6V/19- 34V 43.2V / 38 - 68V
Reduced floating duration - / 0 - 32 days
Periodical absorption - / 0 - 10 hours
Temperature compensation -5 / 0 to -8mV/°C/Cellule (option BTS-01)