STUDER Innotec
Xtender
38 V.3.2.0 User manual
Elem. Description Comment
U Public grid
The connection to the public grid imposes adherence to the local
standards and regulations at the responsibility of the installer. The
installation should, in principle, be checked and approved by an
official body.
V
Automatic
earth-neutral
connection
This connection is deactivated by default. In may be used in certain
specific cases for automatically re-establishing the neutral system type
TT (TNC, TNS, TNC-S) when the Xtender is in inverter mode. The
activation is carried out via RCC-02/03 remote control configuration
{1485}. This operation may only be carried out by qualified personnel,
under the responsibility of these personnel, and in conformity with the
local standards and regulations. See 4.2.3– p.12
W
Galvanic
isolator
This device (optional) is generally used to reduce the risk of electrolytic
corrosion due to the direct current when a boat is connected at the
dock.
X
Source
reversing
switch
When the installation has more than one supply source, it is necessary
to install a switching device between the sources, simultaneously
switching the neutral and the phase(s) of these sources. In all cases this
device (manual or automatic) must guarantee interruption of the
connected source before its connection to another source.
Y
Isolation
transformer
This device (optional) prevents the risk of galvanic corrosion due to
direct currents when a boat is connected at the dock.
14 ELEMENTS OF CONNECT CABINET (FIG 4A)
Pos. Denomination Description Comment
1
ON/OFF
Main switch
Main on/off switch See chapter 7.1 - p 29.
2 Temp. Sens
Connector for the battery
temperature sensor
See chapter 6.4.2 – p. 28.
Only connect the original Studer BTS-
01 sensor
3 Com. Bus
Double connector for
connecting peripherals such as
the RCC002/03 or other
Xtender units
See chapter 4.5.9 – p. 17.
The two termination switches (4) for
the communication bus both
remain
in position T (terminated) except when
both
connectors are in use.
4
O / T
(Open /
Terminated)
Switch for terminating the
communication bus.
5 --
3.3 V (CR-2032) lithium ion type
battery socket
Used as a permanent supply for the
internal clock. See chapter 6.2.11 - p
25.
6 --
Jumper for programming the
off/on switch by dry contact
See chapter 6.2.12 – p. 25 and fig. 8b
point (6) and (7). They are positioned
at A-1/2 and B-2/3 by default
7
REMOTE
ON/OFF
Connection terminals for dry
on/off remote connection.
See chapter 6.2.12– p. 25).
8
AUXILIARY
CONTACT
Auxiliary contact (See chapter 6.2.10– p. 24)
Take care not to exceed the
admissible loads
9 --
Activation indicators for
auxiliary contacts 1 and 2
See chapter 6.2.10– p. 24
10 L1/L2/L3
Phase selection jumpers. See chapter 6.3.1. – p.26.
Jumper default at position L1
11 +BAT
Positive pole battery
connection terminals
Carefully read chapter 4.5 – p.14
Take care with the polarity of the
battery and when tightening the
clamp.
12 -BAT
Negative pole battery
connection terminals