13 FIGURE ELEMENT'S (AC PART)
Elem. Description Comment
A
Input supply
cable
The section is determined by means of the maximum current at source
and the protection device (H). In multi-unit systems, cables (A) of the
same phase must have the same length and section (see comment
fig. 12-2/3).
B
Output supply
cable
In multi-unit systems, cables (B) of the same phase must have the same
length and section (see comment fig. 12-2/3). The section must be
selected by means of the Xtender’s output current given on the type
plate and the protection device selected for the input (see fig. 1a).
C
Connection of
the neutrals
See chapter 4.1.4 - p. 11.
In a fixed installation where the neutral is connected to the earth at a
single installation point upstream of the Xtender, it is permissible to
carry out a connection of the neutrals in order to preserve an
unchanged earthing system downstream, independent of the
operating mode of the Xtender. The downstream protecting ground
fault device.
This connection (C) is not permitted if a socket is installed upstream of
the Xtender.
D
Differential
circuit breaker
A protection device must be installed downstream of he source (G or
U) according to the local requirements and in compliance with the
applicable regulations and standards.
E
Earth-neutral
connection
bridge
The neutral is earthed at a single point of the installation, downstream
of the source and upstream of the protection device(s) at the default
current (DDR). When several sources are available, each source must
have an earthed neutral. If the source has to be retained with an
isolated earthling system (IT) the applicable local provisions and
regulations must be applied.
F
AC output
protection
devices for the
Xtender
A protection device dimensioned in dependence of the cable section
used may be installed downstream of the Xtender (main circuit
breaker before distribution). The cable section is to be dimensioned
according to the calculation table of maximum output current (fig. 1).
The Xtender has an internal current limitation the value of which is
stated on the type plate Fig. 1b (35).
G Generator
The generator is dimensioned according to the requirements of the
user. Its rated current will determine the configuration adjustment
{1107} “maximum current of the AC source”.
H
Protection
devices at the
Xtender input
The protection device at the input of the Xtender must be
dimensioned according to the power output of the source at the
cable section used. It will not exceed a calibre equivalent to the input
current “I AC in” given on the type plate of the unit Fig. 1b (35).
K
Connection
plug / socket
If the Xtender is connected to an AC source by means of a plug, the
connection cable must not exceed a length of 2 m, and the socket
must remain permanently accessible. The socket will be protected by
a protection device of appropriate calibre. The connection of the
neutrals (C) is prohibited in this case.
S Secured grid
Distribution to the users supplied by the grid or the generator when this
is present or by the Xtender within the limit of its power output from
energy stored in the battery. This distribution is carried out in conformity
with the local standards and regulations.
T
Non-secured
grid
Distribution to users supplied exclusively via the present grid or the
generator.
This distribution is carried out in conformity with the local standards and
regulations.