STUDER Innotec
Xtender
42 V.3.2.0 User manual
No. of
config.
Denomination / description Units
Fact.
value
2
Mod.
value
1261 Auxiliary contact 1 activated by power 2 y/n yes
1262 Power 2 above which auxiliary contact 1 is activated % 80
1263 Duration of power 2 for activating auxiliary contact 1 min. 5
1264 Auxiliary contact 1 activated by power 3 y/n no
1265 Power 3 above which will be activated auxiliary contact 1 % 50
1266 Duration of power 3 for activation of auxiliary contact 1 min. 30
1286 Output voltage Vac 230 / 120
1288 Dynamic compensation of the thresholds (AUX.1) y/n no
1298 Increment step of the adaptive low voltage method mV/cell 20
1300 Number of overloads permitted before definite stoppage -- 3
1303
Number of battery over-voltages accepted before definite
stoppage
-- 3
1304
Number of battery under-voltages permitted before final
stop
-- 3
1307 Reset voltage for adaptive correction V/cell 2.2
1309 Minimum ACin voltage to authorise charging Vac 185 / 142
1403 Period for counting battery over-voltages sec. 60
1404 Period for counting battery under-voltages sec. 0
1432 Maximum ACin voltage to switch to inverter mode Vac 270 / 135
1433
Adaptation range of the charge current according to the
input voltage
V 20 / 10
1435 Method of fast detection y/n no
1436
Allow to exceed AC input current without opening the
transfer relay
y/n yes
1470 ACin voltage hysteresis for closing the transfer relay Vac 10 / 5
1485 Automatic earth-neutral connection in inverter mode y/n no
1488 Critical under voltage of the battery V/cell 1.5
1505 Delta of higher frequency accepted Hz 35
1506 Delta of lower frequency accepted Hz 15
1510 Tolerance of fast detection -- 4
1516 Auxiliary contact 1 deactivated by floating mode y/n yes
1517 Auxiliary contact 2 deactivated by floating mode y/n no
1527 Decrease max input limit current with AC-In voltage y/n no
1528 Delay before closing transfer relay Min. 0
1532
Kind of dynamic compensation Auto/
Man
Auto
1547 Allow slave stand-by in multi units system y/n yes
1565 Accoustic alarm duration Sec. 0
To modify the configurations, please refer to the operating instructions for the RCC-02/03
remote control
2
The second value concerns the 120Vac ranges