49
Valid alarms:
--.Not reachable 01.Switched off manually
02.Replaced by 30, 31, 32 03.Replaced by 30, 31, 32
04.Heater error 05.Humidier error
06.Humidier 5uS 07.Humidier 20uS
08.Airow failure 09.Filter contaminated
10.External alarm 11.Pumps error
12.Dry cooler error 13.Water detector
14.Return air temp. too high 15.Return air humidity too high
16.Supply air temp. too high 17.Supply air humidity too high
18.Return air temp. too low 19.Return air humidity too low
20.Supply air temp. too low 21.Supply air humidity too low
22.Replaced by 37, 38, 39 23.Replaced by 40, 41, 42
24.Fire/smoke detector 25.Sensor error
26.Sensor fracture 27.Refrigerant heater failure
28.Phase failure 29.BMS stop 1
30.Refrigerant circuit 1 31.Refrigerant circuit 2
32.Refrigerant circuits 1&2 33.Reserved for CyberCool2
34.Reserved for CyberCool2 35.Reserved for CyberCool2
36.Reserved for CyberCool2 37.Water temp. in 1 high
38.Water temp. in 2 high 39.Water temp. in 1 & 2 high
40.Water temp. in 1 low 41.Water temp. in 2 low
42.Water temp. in 1&2 low
BA C7000 for EC Tower | EN | 01-2019 | 1000755
Config/Zone/More/Valid alarms
(Z3a)
.../Valid alarms (Z3b)
.../Valid alarms (Z3c)
.../Valid alarms (Z3d)
Alarm change-over
So that there is a change-over when alarms occur, alarms can be defined as
valid in menus Z3a, Z3b, Z3c and Z3d by adjusting the parameter to “1”. If this
type of alarm (which is defined as valid) occurs, the defective unit is switched
off and the standby unit with the next highest bus address is switched on. If
another unit with a valid alarm in the zone fails, a further standby unit is switched
on if there is one available.
Some alarms lead to the defective unit being switched off or to certain functions
being deactivated even if the alarm has not been defined as valid (for details,
see chapter “11.4 Alarm texts” on page 72).
The “Unit not reachable” alarm cannot be left out of the configuration and so
always remains valid. This alarm also occurs if the unit is de-energized.