BA C7000 for EC Tower | EN | 01-2019 | 1000755
54
Config
Config/Zone
. Maximum fan speed (nMaxZone) (zone parameter)
This value is not active for the EC tower.
The set speed applies for each unit in the zone if the CW standby manager is activat-
ed and if all units are running. If a unit fails, the remaining units increase their speed
so that the entire airflow rate remains the same. During DFC control or an activated
Ecocool function, this speed nMaxZone is valid in FC operation and is the starting
speed in EFC operation.
. Maximum fan speed (SAPSM) (zone parameter)
This value is not active for the EC tower.
. Valid alarms (zone parameter)
With setting “1”, the affected alarm is defined as a valid alarm for the zone, which
leads to the unit being switched off and it being marked as faulty.