Section 6
SUPERVISOR PROTOCOL
26
21- Value of the parameter (See DATA TYPES)
p – Put parameter Response ##p22,21xx 01p3,49C
The controller’s response to a valid message type P request.
22- Parameter number (See DATA TYPES)
21- Value of the parameter (See DATA TYPES 6 for details)
D – Display Request ##Dxx 01D5B
Monitor’s request for controllers display. The controller responds with d message type.
d – Display Response ##d20,20xx 01d E-STOP , 95 110B7
The controller’s response to a valid message type D request.
20- Display alphanumeric string (See DATA TYPES)
6.7 DATA TYPES
1- P1 pressure in psig, 1 to 3 digits
2- P2 pressure in psig, 1 to 3 digits
3- P3 pressure in psig, 1 to 3 digits
4- P4 pressure in psig, 1 to 3 digits
5- T1 temperature in deg F, 1 to 3 digits
6- T2 temperature in deg F, 1 to 3 digits
7- T3 temperature in deg F, 1 to 3 digits
8- T4 temperature in deg F, 1 to 3 digits
9- T5 temperature in deg F, 1 to 3 digits
10- eConnect ID number, 1 to 2 digits
11- Analog Shutdown (Supervisor II only)
1-4 : P1-P4
5-7 : dP1-dP3
8-13 : T1-T6
12- Digital Outputs, 4 digit (bit0=K1, bit1=K2, etc)
13- Digital Shutdown, 3 digit (bit0=D1, bit1=D2, etc) (Supervisor II only)
14- Digital inputs, 3 digit (bit0=D1, bit1=D2, etc)
15- Total run time in hours, 1 to 6 digits
16- Total load time in hours, 1 to 6 digits
17- Run Status, 1 character code:
E- E-Stop
M- Manual Stop m- Manual Stop & Common Fault
R- Remote Stop r- Remote Stop & Common Fault
B- Standby b- Standby & Common Fault