19
Section 5
SEQUENCING TIMERS
Unload pressure -
All machines unload above this pressure regardless of Recovery timer.
Recovery timer active -
Trim machine will unload after Recovery timer expires.
Sequencing unload pressure -
Trim machine unloads above this pressure, Recovery timer starts.
Sequencing load pressure -
Next machine in sequence loads below this pressure, Recovery timer
starts.
Recovery timer active -
Next machine in sequence loads after Recovery timer expires.
Load pressure -
All machines load below this pressure, Start Delay timer starts.
Start Delay Timer active -
Next machine in sequence starts after Start Delay timer expires.
Lowest Pressure -
Next machine in sequence starts immediately regardless of Start Delay
timer.
5.2 SUMMARY
110
108-110
108
102
100-102
100
70-99
70