EasyManuals Logo

Sumitomo Beier Variator Series User Manual

Sumitomo Beier Variator Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
28
9. Lubricating Oil Cooling Device
9-2) Cooling Water
• For cooling water, use city water or industrial water.
• Table 39 gives a guideling for amount of cooling water supply. Adjust this amount depending on ambient temperature
and operating conditions. It is desirable that Beier Variator be operated with its casing temperature kept within about
60°C .
9-3) Instructions on Starting
• Before starting the main body, be sure to start the oil pump of the lubricating oil cooling device and confirm lubrication.
Allow 30 to 60 seconds lead time for the pump motor, and start the main motor only after the lubricating oil is circulating
well. For the wiring, refer to the diagram on Fig. 11 page14.
9-1) Installation
Install the horizontal-type Beier Variator horizontally, install the vertical-type Beier Variator vertically, and install the
lubricating oil cooling device horizontally.
Install this device as close as possible to the main body of the Beier Variator. If it is installed too far apart, the oil pump
will suffer faulty suction and excessive noise, temperature, and insufficient lubrication will result.
• If air is sucked only halfway out of the suctionside piping of the oil pump, the amount of oil will be reduced as a result of
this insufficient suction, thereby causing excessive noise in the oil pump. For this reason, airtightness must be
mantained.
(1) Install this device within 0.5m in a vertical upward location, or within 1.5m in a vertical downward location, and within 3m
horizontally from main body of the Beier Variator. Minimize pipe bands.
(2) The outline diagram shows both the Beier Variator and its lubricating oil cooling device. According to Fig. 21, install
piping at the site along the broken lines. Use a gas pipe for the piping. Use a 1-1/2B to 2B gas pipe for the Beier Variator
oil outlet, and use a 1B gas pipe for the oil inlet.
Piping materials and pipe joints should be provided by the user since such piping will be installed at the site.
Motor
Oil inlet
Oil inlet
Cooling water outlet
Cooling water intlet
Corrosion preventive zinc rod
Cooling water outlet
Cooling water intlet
Corrosion preventive
zinc rod
Oil filter
Oil outlet
Oil outlet
Oil cooler
Corrosion preventive
zinc rod
Trochoid pump
Pressure
gauge
Pressure
gauge
Oil filter
Oil cooler
Trochoid pump
Corrosion
preventive
zinc rod
Fig. 21
Lubrication oil cooling device is standard attachment to Beier frame size 50A – 200A, 50B – 150B .
COMMON

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sumitomo Beier Variator Series and is the answer not in the manual?

Sumitomo Beier Variator Series Specifications

General IconGeneral
BrandSumitomo
ModelBeier Variator Series
CategoryEngine
LanguageEnglish

Related product manuals