11
Internal components may differ as per selected product module. For details, refer to the
actually received product.
IItteemm
DDeessccrriippttiioonn
RReeccoommmmeennddeedd CCaabbllee
SSppeecciiffiiccaattiioonn
SSoouurrccee
A
RS485
communication
terminal
2 x (0.75~1.5) mm
2
,
outdoor ultraviolet
protection STP
Beyond the scope of
delivery
B PLC1 terminal
4mm²~10mm² or
7~11AWG, withstanding
voltage:
Operating voltage<
800V
To gourd operating
voltage≥1,000V
Beyond the scope of
deliveryC PLC2 terminal
D
220Vac power supply
terminal
Withstanding voltage
315 Vac
1~1.5 mm
2
or
15~17AWG, outdoor
ultraviolet protection
cable
Beyond the scope of
delivery
E
Splice box
User Manual 4 Electrical Connection