82
figure 7-14 PID Parameters
table 7-7 PID Parameter Description
Parameter
Description
PID Recovery
Enabling/Disable the PID night recovery function. Once enabled, it
works between 22:00 pm and 5:00 am by default.
Clear PID alarm
If ISO impedance abnormality or PID function exception is de-
tected during running of the PID function, the inverter reports a
PID abnormity and reminds the user to take corresponding meas-
ures. Clear the alarm report via this parameter once the problems
are handled.
PID Scheme
Apply negative voltage when the inverter is connected to negative
voltage panel.
Apply positive voltage when the inverter is connected to positive
voltage panel.
After the PID night recovery function is enabled, the fault indicator on the inverter
front panel turns green.
AFCI Parameters(Optional)
Tap “Settings→Operation Parameters→AFCI Parameters” to enter the corresponding
screen, on which you can set "AFCI Parameters".
figure 7-15 AFCI Setting
NS Protection(Passive Valid)
Tap “Settings→Operation Parameters→Regular Parameters” to enter the corresponding
screen, on which you can set the "NS Protection(Passive Valid)".
7 iSolarCloud App User Manual