9 Troubleshooting and Maintenance User Manual
60
9.3.2 Fan Cleaning and Replacement
y Disconnect the inverter from the grid first and then PV arrays before any
maintenance work.
y Lethal voltage still exists in the inverter. Please wait at least ten minutes
and then perform maintenance work.
y Fans’ maintenance work may only be performed by qualified electricians.
Fan Cleaning
There is a fan on the rear of the inverter for ventilation. It is recommended that the
fans are cleaned every six months.
Procedure:
1. Disconnect the output and input side.
2. Wait at least ten minutes.
3. Dismantle the inverter in the reversed direction of “Installation procedure.
4. Loosen the two fixed screws on the back of the inverter.
5. Clean the fan with soft brush or vacuum cleaner.
6. Reinstall the inverter.
7. Re-connect the inverter.
8. Restart the inverter.
Fan Replacement
If the fan is overheat or makes an abnormal noise, please replace the fan. This task
should only be performed by qualified technician.

Table of Contents

Other manuals for Sungrow SG3KTL-M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG3KTL-M and is the answer not in the manual?

Sungrow SG3KTL-M Specifications

General IconGeneral
ModelSG3KTL-M
Start Voltage80 V
Number of MPPTs2
Max. AC Power3300 W
Max Efficiency98.1%
European Efficiency97.5%
Cooling TypeNatural convection
Protection DegreeIP65
Rated AC Power3000 W
Maximum AC Output Power3300 W
Rated AC Voltage230 V
Rated AC Output Voltage230 V
AC Voltage Range180-280 V
AC Output Frequency50 Hz / 60 Hz
Operating Temperature Range-25 °C ... +60 °C

Related product manuals