EasyManuals Logo

Sungrow SG3KTL-M User Manual

Sungrow SG3KTL-M
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #89 background imageLoading...
Page #89 background image
81
Technical Specifications SG3KTL-M SG4KTL-M SG5KTL-M
*Valid only when the Pro-param on the LCD
display is set as DE
Protection
Anti-islanding protection Yes
DC reverse connection
protection
Yes
AC short circuit protection Yes
Leakage current protection Yes
DC switch Optional
DC fuse No
Overvoltage protection Varistors
System Data
Max. Efficiency 97.4% 97.6% 97.6%
Max. European efficiency 96.5% 97.0% 97.0%
Isolation method Transformerless
Ingress protection rating IP65 IP65(Fan IP55) IP65(Fan IP55)
Night power consumption <1 W
Operating ambient
temperature range
-25…+60(up 45 derating)
Allowable relative humidity
range
0…95% (No condensing)
Cooling Method
Natural
cooling
Forced air cooling
Max. Working Altitude 4000m(operation with derating above 2000m)
Display Graphic LCD
Communication RS485(RJ45 connector), WiFi(Optional)
DC Terminals SUNCLIX
AC Terminals Plug and play connector (Wieland RST25I3S)
Certification
IEC61000-6-2, IEC61000-6-3,
AS/NZS3100, AS4777.2, AS4777.3,
VDE-AR-N-4105
Mechanical Data
Dimensions(W×H×D) 420×555×179mm
Mounting method Wall bracket
Weight 24kg

Table of Contents

Other manuals for Sungrow SG3KTL-M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG3KTL-M and is the answer not in the manual?

Sungrow SG3KTL-M Specifications

General IconGeneral
BrandSungrow
ModelSG3KTL-M
CategoryInverter
LanguageEnglish

Related product manuals