IGNITION MODULE DIAGNOSTICS
Flame Fault
If at any time the main valve fails to close completely and maintains a flame, the full time flame sense circuit
will detect it and energize the combustion blower. Should the main valve later close completely removing the
flame signal, the combustion blower will power off following the post purge period.
Fault Conditions
Error Mode
LED Indication
Internal Control Failure
Steady On
Air Flow Fault
1 Flash
Gas valve failure (stuck open)
2 Flashes
Ignition Lockout
3 Flashes
The LED located on the ignition module will flash ON
for ¼ second, then OFF for ¼ second during a fault
condition. The pause between fault codes is 3
seconds.
24.0) INSTALLATION DATA
Date of
Installation:
# of Heaters in
System:
Serial
No.
Model:
SPS or SPU
N = Natural Gas
L = Propane Gas