Description
Table 10 Dimensions
Size 250 — 500 Size 630 — 800
Size
A [mm] Ø B [mm] Ø C [mm] Ø D [mm] Ø F [mm] Ø H [mm]
I
AXCBF 250 535 448 328 250 280 10 4x90°
AXCBF 315 535 452 385 320 355 10 8x45°
AXCBF 400 625 585 480 401 450 10 8x45°
AXCBF 500 660 695 590 504 560 12 12x30°
AXCBF 630 790 728 634
-
690 12 12x30°
AXCBF 800 880 890 797
-
860 12 16x22.5°
5.5 Intended use
All axial fans
• The maximum admissible operating data on the name plate apply to an air density of 1.2 kg/3³ (sea level) and a
maximum air humidity of 80%.
• The temperature of the air transported through the fan must not exceed the temperature range stated on the
name plate.
• For the temperature resistance of the smoke extraction fans (K), (B), (F), which can also be used to extract CO,
please refer to the name plate (e.g. 300°C/120 min).
Jet fans
• The model AJ8, AJR and IV jet fans are intended for
installation in underground and above-ground parking
structures, to facilitate ventilation and smoke
extraction (K), (B), (F).
• For optimum operation, the jet fan must be
suspended horizontally from the ceiling in such a
position that intake and outlet are unobstructed.
Axial fans
• The axial fans of the series AXC/AXR/AXCBF in the
versions G (K), (B), (F) are intended for installation in
ventilation systems.
• The axial fans of the series AXC/AXR/AXCBF are
ready-to-use products and are used as components
for ventilation devices, machines and systems. These
fans can be used to extract, draw in or convey air.
• The fans can be installed both in duct systems and
also with free suction via an inlet cone and a suction-
side contact protection grille. Free discharge via a
contact protection grille is also possible.
5.6 Incorrect use
Use the fans only for the requirements described in “intended use” and within the limits for use stated on the name
plate.
• The fan is not suitable for intake of aggressive media or media with a dust content so high that dust deposits on the
impeller or fan housing can affect the operation of the fan.
• The fan must not be installed in hazardous areas (areas with a potentially explosive atmosphere).
• The motors cannot be voltage controlled.