3.2.5 To Install the Grommet and Tubing
Warning
Drilling a metal duct may produce burrs. Be careful not to be cut or pricked by the burrs or the duct.
Caution
Do not connect tubing in such a manner as to allow condensation from the duct to collect in the tubing.
1 Drill a 5/16 inch (8mm) diameter hole in the duct wall.
2 Carefully put the grommet into the hole.
3 Push one end of the tubing over the nipple on the control.
4 Make a mark a distance of 1/2 inch (13mm) from the other end of the tubing.
5 Move this end of the tubing through the center of the grommet up to the mark as shown in the figure from this section.
3
4
5
1
2
6
1. Tubing
2. 1/2 inch (13mm)
3. Grommet
4. Duct Wall
5. 1/4 inch (6mm) maximum
3.2.6 To Connect the Indicator Panel
Cable to the Product
1 Connect the two (2) position connector at the end of the
50–foot (15 meter) indicator panel cable to the receptacle
located on the product’s control box.
8