3060386 | Geniox Air Handling Unit - User Manual
Information about the residual risks | 33
I.1.5 Filters
I.1.5.1 Risk caused by missing change of lters
Hazards/dangerous area:
•Missingchangeofltersandmissingmaintenancedecreasethecapacityandnalconsequencewillbebreakdown.
Dangerous incident:
•Byextensivelackoflterchangeandmaintenancethemachinecanbreakdown.
Claim for reduction of danger:
•Inthemanualisthemethodandscheduleforchangeofltersandmaintenancespecied.
I.1.5.2 Risk caused by the execution of lter change
Hazards/dangerous area:
•Filterpanelsandlterbags
Dangerous incident:
•Tobreatheinparticlesthatisharmfultothehealth.
Claim for reduction of danger:
•Useofparticulaterespirator–maintenancefreeincludingfoamface-sealandadjustablepre-threadedheadbands(sameparticulate
respirator as recommended for cleaning of attenuators.
I.1.6 Plug fans
I.1.6.1 Risk caused by lightning strike
Hazards/dangerous area:
•Lightningstrikeclosetothemachine.
Dangerous incident:
•Lightningstrikecancreateashoverbetweenphasesandconductiveparts.Thiscancausereortheovervoltagecanmakeinjuryon
persons
Claim for reduction of danger:
•Theinstalleranduserneedtobeawareofthesurgeprotectiondevicestheunitwillrequirefromlightningandequivalent.Thetypeof
surge protection will depend on the location of the unit in the building space.
•Installerandusermusttakecareofthisaccordingtolocalstatutoryrequirements.
I.1.6.2 Risk of rotating impeller caused by stack effect (chimney effect).
Hazards/dangerous area:
•Onspecialoccasionsstackeffect–alsocalledchimneyeffect–intheductscreateairowsthatdrivestheimpellersbyturnedoff
motors.
Dangerous incident:
•Injuryofngers,handsandarms.
Claim for reduction of danger:
•Eliminatethisairowforsupplyairandexhaustairbydamperswithspringreturnmotorsforautomaticclosingofthedampersby
turned off fan motors and by power failure.